6 - 15                                                                                                                                                       6 - 15 
MELSOFT
6   COMMUNICATION SETTING EXAMPLES OF THE UTILITY SETTING TYPE 
 
6.2 Ethernet Communication (In case of using Ethernet interface modules) 
This section provides the procedure for Ethernet communication with the Ethernet 
interface module and its setting example using the utility setting type. 
 
6.2.1 Switch settings of Ethernet modules 
This section gives the switch settings of Ethernet modules for the use of MX 
Component. 
 
POINT 
 
When using MX Component, the settings other than "As set by user" in the tables 
are fixed as given in the tables. 
 
(1)  Q series-compatible E71 
Set the Q series-compatible E71 in "MNET/10H Ethernet module count setting" 
of GX Developer. 
 
(2) QE71 
 
Setting 
TCP/IP UDP/IP 
Switch (Switch Number)
 
When ASCII 
packet is used 
When binary 
packet is used 
When binary packet is used 
Operation mode setting switch 
0 (online) 
Line processing selection for 
TCP time-out error (SW1) 
OFF 
Data code setting (SW2) 
ON  
(ASCII code) 
OFF 
(binary code) 
As set by user 
Automatic start mode setting 
(SW3) 
OFF ON 
          —          (SW4 to SW6) 
All OFF 
CPU communications timing 
setting (SW7) 
ON 
Communications 
condition setting 
switches 
Initial timing setting (SW8) 
OFF 
 
(3) E71 
 
Setting 
TCP/IP UDP/IP 
Switch *1
 
When ASCII 
packet is used 
When binary 
packet is used 
When ASCII 
packet is used 
When binary 
packet is used 
Operation mode setting switch 
0 (online) 
Line processing selection for 
TCP time-out error 
OFF 
Data code setting 
ON  
(ASCII code) 
OFF 
(binary code) 
ON  
(ASCII code) 
OFF 
(binary code) 
CPU communications timing 
setting) 
ON 
Communications 
condition setting 
switches 
Initial timing setting 
OFF 
*1: For switch numbers, refer to the E71 module manual.