6   COMMUNICATION SETTING EXAMPLES OF THE UTILITY SETTING TYPE 
 
6.8 CC-Link Communication 
This section provides the CC-Link communication procedure and its setting example 
using the utility setting type. 
 
6.8.1 Accessing procedure 
The procedure for making access to the programmable controller CPU using CC-Link 
communication will be explained in the following order. 
 
START
Set the CC-Link board.
Connect the IBM-PC/AT compatible to CC-Link.
Start the communication setup utility and make
setting on the communication setting wizard.
On the communication test screen, check whether
communication can be made properly.
END
Refer to Chapter 2
and Section 6.8.1 (2).
Refer to Section 6.8.1 (3).
Refer to Section 6.8.1 (4).
 
 
(1) System 
example 
The following system example is used in this section. 
 
CC-Link
Logical station number of "6" is used.
Local station
Station number 1
Number of occupied
stations 4
IBM-PC/AT compatible 
(MX Component) First
CC-Link board is used.
Transmission speed: 10Mbps
Q02H
CPU
Local station
(Sta. No.5)
 
 
Accessible to the FXCPU with CC-Link communication only via the serial/USB 
connection of the QCPU or via the Q series-compatible C24. 
 
Supported CPUs and module in CC-Link communication to FXCPU are as follows. 
CC-Link module 
Compatible CPU 
Station number 
FX
3U
-64CCL FX
3G
,FX
3U(C)
 
1 to 63