Mitsubishi Electronics SW3D5C-ACT-E ユーザーズマニュアル

ページ / 384
 
 
 
APP - 25                                                                                                                                                     APP - 25 
MELSOFT
APPENDICES 
 
Appendix 3.4 FX Series 
The following shows the example of wiring a personal computer and the FX extended 
port.  For details of the FX-485PC-IF converter, refer to the FX SERIES USER’S 
MANUAL-Data Communication Edition. 
 
(1)   Example of connecting a personal computer and FX-485PC-IF 
converter with the RS-232 cable 
 
Personal computer side 
FX-485PC-IF side 
Signal name 
Cable connection and signal direction 
(Full-/Half-Duplex Communication) 
Signal name
Pin No. 
SD(TXD)  
SD(TXD) 
RD(RXD)  
RD(RXD) 
RS(RTS)  
RS(RTS) 
CS(CTS)  
CS(CTS) 
DR(DSR)  
DR(DSR) 
SG(GND)  
SG(GND) 
ER(DTR)  
ER(DTR) 
20 
 
(2)   Example of connecting the FX-485PC-IF converter and the FX 
extended port (2-pair wiring) 
R
*1
R
*1
SDA
SDB
RDA
RDB
LINK SG
SDA
SDB
RDA
SG
SDA
SDB
RDA
SDA
SDB
RDA
RDB
RDB
RDB
FG
*3
FG
*3
R
R
*1
*1
*2
FX-485PC-IF
FX
3U
-485ADP
FX
2N
-485-BD
FX
1N
-485-BD
FX
0N
-485ADP
FX
0N
-485ADP
Grounding
LINK SG
LINK SG
FX
3U
-485-BD
FX
2NC
-485ADP
FX
3G
-485-BD
 
 
*1:    R    indicates a terminal resistance. 
Make sure to install terminal resistances at both ends of the circuit. 
(For 2-pair wiring, use the terminal resistance of 330
Ω, 1/4W.) 
For the FX
3G
-485-BD, FX
3U
-485-BD and FX
3U
-485ADP, terminal resistances are 
built in. 
Set the terminal resistance by the setting switch. 
For the FX
ON
-485ADP, FX
1N
-485-BD, FX
2N
-485-BD, and FX
2NC
-485ADP use the 
provided terminal resistances. 
*2: Make sure to ground the shield connected to the FX
1N
-485-BD, FX
2N
-485-BD, 
FX
2NC
-485ADP, FX
3G
-485-BD, FX
3U
-485-BD, FX
3U
-485ADP. 
*3: Make sure to connect the FG terminal to the ground terminal of the grounded 
programmable controller.