Manitowoc Ice GR-0400A プリント

ページ / 2
 
CONVERSION INSTRUCTIONS 
 
1.  Recover R-502 refrigerant from the ice machine in accordance with local and national governing laws.
 
2.  Refer to “Equipment Modification Requirements” checklist on previous page.
 
3.  Remove and replace liquid line filter drier.  Use only Manitowoc approved OEM filter drier, P/N 8930233.
 
 
NOTE:  compressor oil does not require changing.
 
4.  Evacuate the ice machine.  IMPORTANT:  remote models require a 4-point hose hookup to evacuate 
properly (refer to service manual or service bulletin, SB-18-84, for proper evacuation procedure).
 
5.  Charge ice machine with R-402B refrigerant.  System charge is identical to R-502 charge listed on 
model/serial number tag.  NOTE:  charge with liquid only into the high side of the ice machine using 
weigh-in method or “Dial-A-Charge” (refer to service manual or service bulletin, SB-18-84, for proper 
charging procedure).
 
6.  Remove purple R-502 label near service valves.  Do not remove model and serial number tags!                        
 
7.  Attach an R-402B conversion label, P/N 8134423, to each of the two locations:
 
 
 
A.  Next to the serial number plate.
 
 
 
B.  Next to the service valves.
 
 
IMPORTANT:  write service company name and conversion date on each label.
 
8.  Restart ice machine and verify it operates properly (refer to service manual, if necessary).  Water-cooled 
models maintain head pressure at the same R-502 setting.
 
 
 
 
 
 
 
 
 
 
 
 
 
 
                                                
                                                                                                                                                                                          
        8010513 
   Sheet 2 of 2 
             08/96