YORK INTERNATIONAL
30
FORM 160.55-O1 (604)
OVERVIEW
This screen displays a cutaway view of the Hot Gas By pass 
Valve. All setpoints relating to Hot Gas Bypass con trol are 
maintained on this screen. Also, related Hot Gas Bypass 
control parameters are displayed for ref er ence. Through 
animation, the relative valve position is dis played. In ad-
dition, the valve can be manually op er at ed.
Requires access level of SERVICE. 
Ser vice  Tech ni cians  refer  to  YORK 
Service Man u al 160.55-M1 for op-
 er a tion  in struc tions  and  explanation 
of  all  pro gram ma ble  setpoints  and 
dis played  val ues.
DISPLAY ONLY
Valve Position
Displays the position of the Hot Gas valve over the 
range of 0% (closed) to 100% (fully open). The valve 
position is animated. When the actual position is 0% to 
19%, the valve is shown fully closed. When actual posi-
tion is 20% to 39% the valve is shown 25% open. When 
ac tu al po si tion is 40% to 59%, the valve is shown 50% 
open. When actual position is 60% to 79%, the valve is 
shown as 75% open. Positions greater than 79% shown 
as full open. 
Pre-rotation Vanes Position
Displays the position of the Pre-Rotation Vanes over the 
range of 0% (closed) to 100% (fully open). Dis played 
at XXX until calibration procedure is per formed by 
service technician.
Delta P/P
A parameter that represents system differential or 
“Head”. It is calculated as [(condenser pressure – evap o -
ra tor pressure) / evaporator pressure].
Temperature Differential
The difference between the Leaving Chilled Liquid Tem-
 per a ture  and  the  Leaving  Chilled  Liquid  Tem per a ture 
Setpoint. It is cal cu lat ed by sub tract ing the Leav ing 
Chilled  Liq uid  tem per a ture  from  the  Leav ing  Chilled 
Liquid  Tem per a ture  Setpoint.
Total Surge Count
This is the total number of surge events that have been 
detected over the lifetime of the chiller. These are the 
surge events detected by the Surge Protection feature. 
The surge events detected by the compressor Variable 
Speed Drive Adaptive Capacity Control Board are not 
included in this total.
Surge Detected (LED)
Illuminated for 5 seconds each time a surge is detected 
by the Surge Protection feature. It does not illuminate 
FIG. 11
HOT GAS BYPASS SCREEN
OptiView Control Center
00476VIP