OIL SUMP SCREEN
OVERVIEW
This screen displays a close-up of the chiller oil 
sump. 
DISPLAY ONLY
Oil Sump Temperature
Displays the temperature of the oil in the sump.
Oil Pressure 
Displays the pressure differential between the high side 
oil pressure transducer (output of oil Þ lter) and the low 
side oil pressure transducer (compressor housing). If 
either of the transducers used to calculate this dif fer -
en tial is out of range, the display Þ eld will show XX.X. 
Oil Pump Run Output (LED)
Indicates whether the Oil Pump is being commanded 
to operate.
Manual Oil Pump Operation Time Left
Displays the time remaining in the 10-minute manual 
oil pump operation described below.
PROGRAMMABLE
Manual Pump  
 
 
 
 
 
Access Level Required: OPERATOR
This key puts the Oil Pump control in Manual Mode and 
forces it to RUN. The Oil Pump is limited to run ning for 
a maximum of ten (10) minutes. If a longer running time 
is desired, this key must be pressed again. Manual Oil 
Pump control is disabled (and the button hidden) during 
system prelube, system run and system coastdown.
NAVIGATION
Home   
 
 
 
 
 
Access Level Required: VIEW
Causes an instant return to the Home Screen.