MOD “B” SOLID STATE STARTER SCREEN
00359VIP
FIG. 18
OVERVIEW
This screen displays all information pertaining to the 
Mod “B” Solid State Starter.
DISPLAY ONLY
Motor Run (LED)
Indicates whether the digital output from the controls is 
commanding the motor to RUN.
Motor Current % Full Load Amps
Displays the motor current as a percentage of the Full 
Load Amps (FLA) value.
Current Limit Setpoint
Displays the current limit in use. This value could come 
from a 0-20mA, 4-20mA, 0-10VDC or 2-10VDC input 
in Analog Remote Mode, PWM signal in Digital Re mote 
Mode, MicroGateway interface in ISN remote Mode or 
a lo cal ly programmed value in Local Mode.
Pulldown Demand Time Left
Displays the time remaining in the programmed pull-
down period.
Input Power
Displays the Kilowatts measured by the Solid State 
Start er.
kW Hours
Displays the cumulative amount of kilowatts used over 
time.
Starter Model
Displays the Solid State Starter model that is applied to 
the chiller. Starter Models are 7L, 14L, 26L or 33L.
Voltage – Phase A, B, C
Displays the 3-phase input line voltage measured by the 
Solid State Starter.
Current – Phase A, B, C
Displays the 3-phase motor current values measured by 
the Solid State Starter.
Temperature – Phase A, B, C
Displays the temperatures of the Silicon Controlled 
Rec ti Þ  er assemblies.
PROGRAMMABLE
Local Motor Current Limit
Access Level Required: OPERATOR
Allows the user to specify the maximum al lowed mo tor 
current (as percentage of FLA). When the mo tor cur rent 
reaches this value, the Pre-rotation Vanes will not be 
permitted to open fur ther. If the motor rises above this 
value, the Pre-ro ta tion Vanes will close to reduce the 
current to this value.
OptiView Control Center