TREND SETUP SCREEN
OVERVIEW
 
This screen is used to conÞ gure the trending screen. 
The parameters to be trended are selected from the 
Common Slots Screen or Common Slots Master list 
and entered as Slot Numbers for Data Points 1 through 
6. The Y-Axis minimum and maximum values for each 
parameter are entered as Data Point Min and Data Point 
Max for Data Points 1 through 6. The interval at which 
all the parameters are sampled is selected as the Data 
Collection Interval.
DISPLAY ONLY
None
PROGRAMMABLE
Chart Type
Access Level Required: OPERATOR
(Flash Memory Card version (C.MLM.02.02.xxx and 
lat er)  Selects CONTINUOUS, ONE SCREEN or 
TRIG GERED type of graph. 
Collection Interval
Access Level Required: OPERATOR
Selects the interval at which the parameters are sam pled. 
There are 450 data points displayed across the X-Axis 
of the graph. Each point represents the instantaneous 
value of the parameter. The user selects the time in-
 ter val between these points. This is called the DATA 
COL LEC TION INTERVAL or the interval at which the 
pa ram e ter is sampled. This interval is programmable 
over the range of 1 second to 3600 seconds (1 hour), in 
one second increments. The selected interval not only 
de ter mines the sample interval, but also the full screen 
time display. The full screen time display is a result of the 
selected interval in seconds, multiplied by the 450 data 
points. For example, if the Data  Collection  In ter val is 
programmed for 900 seconds, the parameter would be 
sampled every 900 seconds, with the last 112.5 hours 
(4.7 days) of data viewable on the screen. There fore, the 
selected interval is a compromise between res o lu tion 
and full screen time display. Select the desired Data 
Collection Interval
 as follows:
 1. Determine the desired time interval (in sec onds), 
be tween data samples. 
 2. Calculate the full screen time display as follows:
      450 x Data Collection Interval = full screen sec onds
      full screen seconds / 60 = full screen minutes
      full screen minutes / 60 = full screen hours
      full screen hours / 24 = full screen days
  3. Decide if the resultant sample interval and full screen 
display meet the requirements. If not, select a dif-
 fer ent  sample  interval. 
00481VIP
FIG. 38
OptiView Control Center