GP Series Portable Chillers 
Chapter 2: Functional Description 
15 of 90 
Stainless Steel Reservoir. Manufactured from 304 stainless steel. 
Mounting Features.  
Mounting rails with feet – GP20-GP105 indoor units.  Standard on GP140-GP210 and all 
outdoor packaged units. 
Optional Operating Voltages. 208-230/3/60, 460/3/60, 575/3/60, and 400/3/50 volt 
available  
UL/cUL Labeled Electrical Subpanel.  This option provides for the subpanel to be listed 
with Underwriters Laboratory, with UL-related benefits and features.  Sub-panels marked by 
the UL/cUL sticker are accepted within Canada. 
Optional Pumps. Pump options are available for greater pressure and flow rates. A 
recirculation pump is required whenever process water flow is less than 1.2 gpm per ton or 
greater than 4.8 gpm per ton. See Figure 1 below for optional pump amperages. 
 
 
Figure 1: Optional Pump Amperages 
Voltage 
Construction 
HP (kW) 
Full Load Amps 
460/3/60 
SS 
1 (0.8) 
1.7 
 
 
1.5 (1.1) 
2.3 
 
 
2 (1.5) 
4.0 
 
 
3 (2.2) 
4.2 
 
 
5 (3.7) 
8.2 
 
 
7.5 (5.6) 
10.3 
 
 
10 (7.5) 
12.0 
 
 
15 (11) 
20.0 
 
 
30 (22) 
32.0