Chapter 4: Operation 
24 of 44 
 
 
Enter the established Operator Password by depressing the 
 to move the 
position of the cursor, and then depressing the 
  or 
 button to 
increment or decrement the number.  Once all of the numbers have been 
entered depress the 
 to accept the password. The following screen will 
appear. 
 
Figure 6 - Operator Setpoints Screen 
5.  Depress 
 to move the cursor to the Leaving Temp line.  Use the 
 or 
 button to increment or decrement the value.  Depress 
 to accept the 
value and move the cursor down one line. 
6.  Depress the 
 button twice to return to the main status screen. 
7.  Depress the 
 to start the chiller. 
8.  Check pump rotation 
9.  Check the pump amp draw and pump pressure. Make sure that the amp draw 
reading is within the running load and service factor amps. 
10.  Operate the chiller, looking for any leaks and listening for unusual noises or 
vibrations that could indicate improper operation.