Mitsumi electronic FR-CV-7.5K to 30K(-AT) ユーザーズマニュアル

ページ / 63
27
Other wiring
INS
TALL
A
TION AND WIRING
2
(2) Selection the rated sensitivity current for the earth leakage circuit breaker
When using the earth leakage circuit breaker with the inverter circuit, select its rated sensitivity current as follows,
independent of the carrier frequency setting:
z Breaker for harmonic and surge 
Rated sensitivity current:
   l
Δn ≥ 10  × (lg
1
 + lgn + lg
2
 + lgm) 
z Standard breaker 
Rated sensitivity current: 
   l
Δn  ≥ 10  × {lg
1
 + lgn + 3 × (lg
2
+lgm)} 
   lg
1
, lg
2
: leakage currents of cable path during
  commercial power supply operation 
   lgn*
: leakage current of noise filter on power
regeneration common converter input
side 
   lgm
: leakage current of motor during 
  commercial power supply operation  
<Example>
* Be careful of the leakage current value of the noise filter installed on the power regeneration common
converter input side.
Breaker for 
Harmonic and Surge
Standard Breaker
Leakage current Ig1 (mA)
50 
×  
=0.25 
Leakage current Ign (mA)
0 (without noise filter)
Leakage current Ig2 (mA)
50 
×  
=1.50 
Motor leakage current Igm (mA)
0.57
Total leakage current (mA)
2.32
6.46
Rated sensitivity current (mA) ( 
≥Ig × 10)
30
100
Note: 1. The NV should be installed to the primary (power supply) side of the power regeneration common
converter. 
2. Ground fault in the secondary side of the inverter can be detected at the running frequency of 120Hz or
lower. 
3. In the   connection neutral point grounded system, the sensitivity current becomes worse for ground
faults in the inverter secondary side. Hence, the protective grounding of the load equipment should be
10
Ω or less.
4. When the breaker is installed on the secondary side of the inverter, it may be unnecessarily operated by
harmonics if the effective value is less than the rating. In this case, do not install it since the eddy current
and hysteresis loss increase and the temperature rises.
5. The following models are standard breakers 
BV-C1, BC-V, NVB, NV-L, NV-G2N, NV-G3NA, and NV-2F type leakage current relays (except for
NV-ZHA), AA neutral wire, NV with open phase protection 
The following models are breakers for harmonic and surge 
NV-C/NV-S/MN series, NV30-FA, NV50-FA, BV-C2, leakage current alarm breaker(NF-Z), NV-ZHA,
NV-H
0
20
40
60
80
100
120
2 3.5
5.5
8 14 22
30
38
60
80
100
150
0.1
1.5
3.7
2.2
7.5 15 22
11
37
30
55
45
0.2
0.3
0.5
0.7
1.0
2.0
5.5
18.5
Example of leakage current 
per 1km in cable path during 
commercial power supply
operation when the CV 
cable is routed in metal 
conduit (200V 60Hz)
Leakage current example
of 3-phase induction motor
during commercial power
supply operation
(200V 60Hz)
Leak
age cu
rr
ent
 (
m
A
)
Leak
age cu
rr
ent
 (
m
A
)
Cable size (mm  )
2
Motor capacity (kW)
NV
Ig1
Ign
Ig2
Igm
IM
22mm
2
×5m
(16.40 feet)
22mm
2
×30m
(98.43 feet)

200V
15kW (20HP)
Noise
filter
+
Inverter
Power regeneration
common converter
15K
5m (16.40 feet)
1000m (3280.80 feet)
30m (98.43 feet)
1000m (3280.80 feet)