Mitsumi electronic FR-CV-H7.5K to H30K(-AT) ユーザーズマニュアル

ページ / 63
45
Standard Specifications
SPECIF
ICA
TIONS
4
400V class 
T
ype 
Heat sink outside mounting 
structure
FR-CV-H
K
7.5
11
15
22
30
37
(Note 4)
55
(Note 4)
Enclosure inside installation 
structure
FR-CV-H
K-AT
Applicable inverter 
capacity (Note 1)
kW
7.5
11
15
22
30
37
55
HP
10
15
20
30
40
50
75
Outp
ut
Applicable current (A) (Note 1)
17
23
31
43
57
71
110
Regenerative 
braking torque
Short-duration 
rating
150% torque 60s
Continuous 
rating
100% torque
Power supp
ly
Rated input AC voltage, 
frequency
Three phase 380 to 480V 50Hz/60Hz
Permissible AC voltage 
fluctuation
Three phase 323 to 528V 50Hz/60Hz
Permissible frequency 
fluctuation
±5%
Power supply system capacity 
(kVA)  (Note 2)
17
20
28
41
52
66
100
Protective structure  (JEM 1030)
Open type (IP00)
Cooling system
Self-
cooling
Forced air cooling
Approximately weight 
(kg (lbs))
Heat sink 
outside 
mounting 
structure
6.0
(13.2)
6.0
(13.2)
6.0
(13.2)
10.0
(22.0)
10.0
(22.0)
32.5
(71.7)
32.5
(71.5)
Enclosure 
inside 
installation 
structure
7.5
(16.5)
7.5
(16.5)
7.5
(16.5)
13.0
(28.7)
13.0
(28.7)
Input signal
Reset
Output signal
Ready output signal, inverter run enable signal, converter reset, alarm signal
Protective functions
Overcurrent protection, overvoltage protection, electronic overcurrent protection, 
undervoltage, phase failure, CPU alarm, instantaneous power failure alarm, power 
supply alarm
Environment
Ambient temperature
-10°C to +50°C (14°F to 122°F) (non-freezing)
Ambient humidity
90%RH or less (non-condensing)
Storage temperature
-20°C to 50°C (-4°F to 122°F)
Ambience
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Altitude
Maximum 1000m (3280.80feet) above sea level for standard operation.
After that derate by 3% for every extra 500m (1640.40feet) up to 2500m 
(8202.00feet) (91%).
Vibration
5.9m/s
or less
Dedicated stand-alone reactor
FR-CVL-
H7.5K
FR-CVL-
H11K
FR-CVL-
H15K
FR-CVL-
H22K
FR-CVL-
H30K
FR-CVL-
H37K
FR-CVL-
H55K