Instruction Manual Supplement
When installing a thermal relay to the cooling fan of the vector-control dedicated motors (SF-
V5RU), use the following recommended thermal relay settings.
V5RU), use the following recommended thermal relay settings.
200V class (Mitsubishi dedicated motor [SF-V5RU (1500r/min series)])
400V class (Mitsubishi dedicated motor [SF-V5RUH (1500r/min series)])
*1 Power (current) at 50Hz/60Hz.
*2 The cooling fan is equipped with a thermal protector. The cooling fan stops when the coil temperature exceeds
*2 The cooling fan is equipped with a thermal protector. The cooling fan stops when the coil temperature exceeds
the specified value in order to protect the fan motor. A restrained cooling fan or degraded fan motor insulation
may causes the rise in coil temperature. The fan motor re-starts when the coil temperature drops to normal.
may causes the rise in coil temperature. The fan motor re-starts when the coil temperature drops to normal.
*3 The voltage and input values are the standard specifications of the cooling fan in free air. When the cooling fan
is used with a motor, it requires more energy to perform its work, and thus the above input values become
slightly larger. The cooling fan can, however, be used as it is without causing problems. When a thermal relay is
to be prepared at the customer's side, use the recommended thermal relay settings.
slightly larger. The cooling fan can, however, be used as it is without causing problems. When a thermal relay is
to be prepared at the customer's side, use the recommended thermal relay settings.
Motor type
SF-V5RU
K
1
2
3
5
7
11
15
18
22
30
37
45
55
Cooling fan (with
thermal protector)*2*3
thermal protector)*2*3
Voltage
Single-phase 200V/50Hz
Single-phase 200V to 230V/60Hz
Three-phase 200V/50Hz
Three-phase 200 to 230V/60Hz
Input *1
36/55W
(0.26/0.32A)
22/28W
(0.11/0.13A)
55/71W
(0.37/0.39A)
100/156W
(0.47/0.53A)
85/130W
(0.46/0.52A)
Thermal relay
settings
0.36A
0.18A
0.51A
0.69A
0.68A
Motor type
SF-V5RUH
K
1
2
3
5
7
11
15
18
22
30
37
45
55
Cooling fan (with
thermal protector)*2*3
thermal protector)*2*3
Voltage
Single-phase 200V/50Hz
Single-phase 200V to 230V/60Hz
Three-phase 380 to 400V/50Hz
Three-phase 400 to 460V/60Hz
Input *1
36/55W
(0.26/0.32A)
22/28W
(0.11/0.13A)
55/71W
(0.19/0.19A)
100/156W
(0.27/0.30A)
85/130W
(0.23/0.26A)
Thermal relay
settings
0.36A
0.18A
0.25A
0.39A
0.34A