Mitsubishi Electronics FR-A740-0.4k to 500k ユーザーズマニュアル
71
Param
e
te
r List
Parameter List
4
4.2 Parameter List
4.2.1
Parameter list
For simple variable-speed operation of the inverter, the initial value of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made
from the operation panel (FR-DU07).
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made
from the operation panel (FR-DU07).
REMARKS
⋅
indicates simple mode parameters. (initially set to extended mode)
⋅
The shaded parameters in the table allow its setting to be changed during operation even if "0" (initial value) is set in Pr. 77 Parameter write
selection.
selection.
⋅
Refer to Appendix 2 (page 466) for instruction codes for communication and availability of parameter clear, all clear, and parameter copy of
each parameter.
⋅
Parameters with
have different specifications according to the date assembled. Refer to page
to check the SERIAL number.
Func-
tion
Parameter
Name
Setting Range
Minimum
Setting
Increments
Initial Value
Refer
to
Page
Customer
Setting
Ba
si
c f
unc
tions
0
Torque boost
0 to 30%
0.1%
6/4/3/2
/1%
*1
1
Maximum frequency
0 to 120Hz
0.01Hz
120
/60Hz
*2
2
Minimum frequency
0 to 120Hz
0.01Hz
0Hz
3
Base frequency
0 to 400Hz
0.01Hz
60Hz
4
Multi-speed setting (high speed)
0 to 400Hz
0.01Hz
60Hz
5
Multi-speed setting (middle speed)
0 to 400Hz
0.01Hz
30Hz
6
Multi-speed setting (low speed)
0 to 400Hz
0.01Hz
10Hz
7
Acceleration time
0 to 3600/360s
0.1/0.01s
5/15s
*3
8
Deceleration time
0 to 3600/360s
0.1/0.01s
5/15s
*3
9
Electronic thermal O/L relay
0 to 500/0 to 3600A
*2
0.01
/0.1A
*2
Rated inverter
current
D
C inj
e
ct
io
n
brak
e
10
DC injection brake operation frequency 0 to 120Hz, 9999
0.01Hz
3Hz
11
DC injection brake operation time
0 to 10s, 8888
0.1s
0.5s
12
DC injection brake operation voltage
0 to 30%
0.1%
4/2
/1%
⎯
13
Starting frequency
0 to 60Hz
0.01Hz
0.5Hz
⎯
14
Load pattern selection
0 to 5
1
0
Jog
op
erat
ion
15
Jog frequency
0 to 400Hz
0.01Hz
5Hz
16
Jog acceleration/deceleration time
0 to 3600/360s
0.1/0.01s
0.5s
⎯
17
MRS input selection
0, 2, 4
1
0
⎯
18
High speed maximum frequency
120 to 400Hz
0.01Hz
120
/60Hz
*2
⎯
19
Base frequency voltage
0 to 1000V, 8888, 9999
0.1V
9999
A
cce
le
ra
tio
n
/
de
ce
le
ra
tio
n
ti
m
e
s
20
Acceleration/deceleration reference
frequency
frequency
1 to 400Hz
0.01Hz
60Hz
21
Acceleration/deceleration time
increments
increments
0, 1
1
0
St
a
ll
pr
ev
ent
ion
22
Stall prevention operation level
(torque limit level )
0 to 400%
0.1%
150%
23
Stall prevention operation level
compensation factor at double speed
0 to 200%, 9999
0.1%
9999
Mu
lti
-s
peed
se
tt
in
g
24 to 27
Multi-speed setting(4 speed to 7 speed)
0 to 400Hz, 9999
0.01Hz
9999
⎯
28
Multi-speed input compensation selection
0, 1
1
0
⎯
29
Acceleration/deceleration pattern
selection
0 to 5
1
0
⎯
30
Regenerative function selection
0, 1, 2, 10, 11, 20, 21
1
0
F
req
uen
cy
ju
mp
31
Frequency jump 1A
0 to 400Hz, 9999
0.01Hz
9999
32
Frequency jump 1B
0 to 400Hz, 9999
0.01Hz
9999
33
Frequency jump 2A
0 to 400Hz, 9999
0.01Hz
9999
34
Frequency jump 2B
0 to 400Hz, 9999
0.01Hz
9999
35
Frequency jump 3A
0 to 400Hz, 9999
0.01Hz
9999
36
Frequency jump 3B
0 to 400Hz, 9999
0.01Hz
9999
⎯
37
Speed display
0, 1 to 9998
1
0