Mitsubishi Electronics FR-D740-012 ユーザーズマニュアル

ページ / 294
11
Installation of the inverter and enclosure design
1.4.3
Inverter placement
(1) Installation of the inverter
Enclosure surface mounting
Remove the front cover and wiring cover to fix the inverter to the surface.
(2) Clearances around inverter
(3) Inverter mounting orientation
Mount the inverter on a wall as specified. Do not mount it horizontally or any other way.
(4) Above inverter
Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed above the inverter should be
heat resistant.
NOTE
When encasing multiple inverters, install them in parallel as a
cooling measure.
Install the inverter vertically.
To ensure ease of heat dissipation and maintenance, leave at least the shown clearances around the inverter. At least the
following clearances are required under the inverter as a wiring space, and above the inverter as a heat dissipation space.
Front cover
Front cover
Wiring cover
Wiring cover
FR-D720-070 or more
FR-D740-012 or more
FR-D720S-070, 100
FR-D720-008 to 042
FR-D720S-008 to 042
V
e
rtical
Refer to th
e clearances belo
w.
Surrounding air temperature and humidity
Measurement  
position
Measurement
position
Inverter
5cm
(1.97inches)
5cm
(1.97inches)
5cm (1.97inches)
Humidity: 90% RH maximum
Clearances (side)
1cm 
(0.39
inches)
or more
*
Inverter
Clearances (front)
10cm 
(3.94inches) 
or more
10cm 
(3.94inches) 
or more
1cm 
(0.39inches)
 
or more*
1cm 
(0.39inches)
  
or more*
* 5cm (1.97inches) or more for 
the FR-D720-238 or more 
and FR-D740-120 or more
Leave enough clearances and take 
cooling measures.
Temperature: -10 C to +50 C
                         (14 F to 122 F)
* When using the inverters at the surrounding air 
temperature of 40 C (104 F) or less, the inverters can 
be installed without any clearance between them 
(0cm (0inch) clearance).
  When surrounding air temperature exceeds 40 C 
(104 F), clearances between the inverters should be 
1cm (0.39inches) or more (5cm (1.97inches) or more 
for the FR-D720-238 or more and FR-D740-120 or 
more).