Measurement of main circuit voltages, 
currents and powers
Measuring points and instruments
*1
Use an FFT to measure the output voltage accurately. A tester or general measuring instrument cannot measure accurately.
*2
When the carrier frequency exceeds 5kHz, do not use this instrument since using it may increase eddy-current losses produced in metal parts
inside the instrument, leading to burnout. If the wiring length between the inverter and motor is long, the instrument and CT may generate
heat due to line-to-line leakage current.
*3
When the setting of Pr. 195 ABC1 terminal function selection is positive logic
*4
A digital power meter (designed for inverter) can also be used to measure.
Item
Measuring Point
Measuring Instrument
Remarks (Reference Measured Value)
Power supply voltage
V
1
Across R/L1 and S/
L2, S/L2 and T/L3, 
T/L3 and R/L1
Moving-iron type AC 
voltmeter 
*4
Commercial power supply
Within permissible AC voltage fluctuation 
(Refer to page 182)
Power supply side 
current
I
1
R/L1, S/L2, and T/L3 
line currents
Moving-iron type AC 
ammeter 
*4
Power supply side 
power
P
1
R/L1, S/L2, T/L3 and 
R/L1 and S/L2, 
S/L2 and T/L3, 
T/L3 and R/L1
Digital power meter 
(designed for inverter) or 
e
lectrodynamic type 
single-phase wattmeter
P1=W11+W12+W13 (3-wattmeter method)
Power supply side 
power factor
Pf
1
Calculate after measuring power supply voltage, power supply side current and power supply side power.
Output side voltage
V
2
Across U and V, 
V and W 
and W and U
Rectifier type AC voltage 
meter 
*1
 
*4 
(Moving-iron type cannot 
measure)
Difference between the phases is within ±1% of the 
maximum output voltage.
Output side current
I
2
U, V and W line 
currents
Moving-iron type AC 
ammeter 
*2
 
*4
Difference between the phases is 10% or lower of the 
rated inverter current.
Output side power
P
2
U, V, W and 
U and V, 
V and W
Digital power meter 
(designed for inverter) or 
e
lectrodynamic type 
single-phase wattmeter
P
2
 = W
21
 + W
22
2-wattmeter method (or 3-wattmeter method)
Output side power 
factor
Pf
2
Calculate in similar manner to power supply side power factor.
Converter output
Across P/
+ and N/−
Moving-coil type (such as 
tester)
Inverter LED display is lit. 1.35 
×
 V1
Frequency setting 
signal
Across 2 and 5
Across 4(+) and 5
Moving-coil type
 (Tester and such may be 
used)
(Internal resistance: 
50k
Ω or larger)
0 to 10VDC, 4 to 20mA
"5" is 
common
Across 1(+) and 5
0 to ±5VDC, 0 to ±10VDC
Frequency setting 
power supply
Across 10 (+) and 5
5.2VDC
Across 10E(+) and 5
10VDC
Frequency meter 
signal
Across AM(+) and 5
Approximately 10VDC at maximum frequency
(without frequency meter)
Across FM(+) and SD
Approximately 5VDC at maximum frequency 
(without frequency meter)
Pulse width T1:
Adjusted by C0 (Pr. 900)
Pulse cycle T2: Set by Pr. 55
(Valid for frequency monitoring only)
"SD" is 
common
Start signal
Select signal
Across SD and the 
following:
STF, STR, RH, RM, 
RL, JOG, RT, AU, 
STOP, CS (+)
When open
20 to 30VDC
ON voltage: 1V or less
Reset
Across RES (+) and SD
Output stop
Across MRS (+) and SD
Alarm signal
Across A1 and C1
Across B1 and C1
Moving-coil type 
(such as tester)
Electric continuity check
*3
<Normal>
<Abnormal>
Across A1-C1 Discontinuity
Continuity
Across B1-C1
Continuity
Discontinuity
Pf
1
 = ————— 
× 100%
P
1
V
× I
1
Pf
2
 = ————— 
× 100%
P
2
V
× I
2
8VDC
T1
T2