Mitsubishi Electronics FR-A701 ユーザーズマニュアル

ページ / 259
22
Control circuit specifications
*2
Refer to Chapter 4 of 
 the Instruction Manual (Applied).
(3) Communication
Op
en
 c
o
lle
cto
r
RUN
Inverter 
running
Switched low when the inverter output frequency is equal to or 
higher than the starting frequency (initial value 0.5Hz). Switched 
high during stop or DC injection brake operation.
 
Permissible load  
24VDC (27VDC 
maximum) 0.1A
(A voltage drop is 
2.8V maximum 
when the signal is 
on.)
*1 Low is when the 
open collector 
output transistor is 
ON (conducts).
High is when the 
transistor is OFF 
(does not 
conduct).
SU
Up to 
frequency
Switched low when the output 
frequency reaches within the range of 
±10% (initial value) of the set frequency.  
Switched high during acceleration/
deceleration and at a stop.
Alarm code (4bit) 
output 
OL
Overload 
warning
Switched low when stall prevention is 
activated by the stall prevention 
function.  Switched high when stall 
prevention is cancelled. 
IPF
Instantaneous 
power failure
Switched low when an instantaneous 
power failure and under voltage 
protections are activated. 
FU
Frequency 
detection
Switched low when the inverter output 
frequency is equal to or higher than the 
preset detected frequency and high 
when less than the preset detected 
frequency. 
SE
Open collector 
output common
Common terminal for terminals RUN, SU, OL, IPF, FU
--------------------
-----
Pu
lse FM
For meter
Select one e.g. output frequency from 
monitor items. Not output during 
inverter reset.
The output signal is proportional to the 
magnitude of the corresponding 
monitoring item.
To set a full-scale value for monitoring 
the output frequency and the output 
current, set Pr. 56 and Pr.158
*2
Output item: 
Output frequency 
(initial setting)
Permissible load 
current 2mA
1440pulses/s at 
60Hz
NPN open 
collector output
Signals can be output 
from the open 
collector terminals by 
setting Pr. 291.
Maximum output 
pulse: 50kpulses/s
Permissible load 
current : 80mA
A
nal
og
AM
Analog signal 
output
Output item: 
Output frequency 
(initial setting)
Output signal 0 to 
10VDC
Permissible load 
current 1mA
(load impedance 
10k
Ω or more) 
Resolution 8 bit
Ty
p
e
Terminal 
Symbol
Terminal 
Name
Description
Refer to 
page
RS-4
8
5
--------------------
 PU 
connector
With the PU connector, communication can be made through RS-485.
(for connection on a 1:1 basis only)
. Conforming standard : EIA-485 (RS-485)
. Transmission format
: Multidrop link
. Communication speed : 4800 to 38400bps
. Overall length
: 500m
RS-4
8
5 t
e
rm
in
a
ls
TXD+
Inverter 
transmission 
terminal
With the RS-485 terminals, communication can be made through RS-485.
Conforming standard
: EIA-485 (RS-485)
Transmission format
: Multidrop link
Communication speed : 300 to 38400bps
Overall length
: 500m
TXD-
RXD+
Inverter 
reception 
terminal
RXD-
SG
Earth (Ground)
USB
--------------------
USB 
connector
The FR Configurator can be used by connecting the inverter to the personal 
computer through USB.
Interface:Conforms to USB1.1
Transmission speed:12Mbps
Connector:USB B connector (B receptacle)
Ty
p
e Terminal
Symbol
Terminal 
Name
Description
Rated 
Specifications
Refer to 
page