Mitsubishi Electronics FR-A701 ユーザーズマニュアル

ページ / 259
38
EMC and leakage currents
z
 Data line filter
Data line filter is effective as an EMC measure. Provide a data line filter for the detector cable, etc.
z
 EMC measures
Propagation Path
Measures
1) 2) 3)
When devices that handle low-level signals and are liable to malfunction due to electromagnetic noises, 
e.g. instruments, receivers and sensors, are contained in the enclosure that contains the inverter or when 
their signal cables are run near the inverter, the devices may be malfunctioned by air-propagated 
electromagnetic noises. The following measures must be taken:
(1) Install easily affected devices as far away as possible from the inverter.
(2) Run easily affected signal cables as far away as possible from the inverter and its I/O cables.
(3) Do not run the signal cables and power cables (inverter I/O cables) in parallel with each other and do 
not bundle them.
(4) Insert common mode filters into I/O and capacitors between the input lines to suppress cable- 
radiated noises.
(5) Use shield cables as signal cables and power cables and run them in individual metal conduits to 
produce further effects.
4) 5) 6)
When the signal cables are run in parallel with or bundled with the power cables, magnetic and static 
induction noises may be propagated to the signal cables to malfunction the devices and the following 
measures must be taken:
(1) Install easily affected devices as far away as possible from the inverter.
(2) Run easily affected signal cables as far away as possible from the I/O cables of the inverter.
(3) Do not run the signal cables and power cables (inverter I/O cables) in parallel with each other and do 
not bundle them.
(4) Use shield cables as signal cables and power cables and run them in individual metal conduits to 
produce further effects.
7)
When the power supplies of the peripheral devices are connected to the power supply of the inverter in 
the same line, inverter-generated noises may flow back through the power supply cables to malfunction 
the devices. In such a case, installing the common mode filter (FR-BLF) to the power cables (output 
cable) of the inverter will prevent malfunction.
8)
When a closed loop circuit is formed by connecting the peripheral device wiring to the inverter, leakage 
currents may flow through the earth (ground) cable of the inverter to malfunction the device. In such a 
case, disconnection of the earth (ground) cable of the device may cause the device to operate properly.
Inverter
Sensor
Use 4-core cable for motor 
power cable and use one 
cable as earth (ground) cable.
Use a twisted pair shielded cable
Inverter
power
supply
Control
power
supply
Do not earth (ground) shield but 
connect it to signal common cable.
Enclosure
Decrease
carrier frequency
Motor
IM
FR-
BLF
FR-
BLF
FR-
BIF
Do not earth (ground) 
enclosure directly.
Do not earth (ground) control cable.
Separate inverter and power
line by more than 30cm (at
least 10cm) from sensor circuit.
Install common mode filter (FR-BLF)
on inverter output side.
Install capacitor type FR-BIF filter
on inverter input side.
Install common mode filter (FR-BLF)
on inverter input side.
Power
supply
for sensor