Mitsubishi Electronics FR-A701 ユーザーズマニュアル

ページ / 259
58
4.3.3
When the rated motor frequency is 50Hz (Pr. 3) 
First, check the motor rating plate. If a frequency given on the rating plate is "50Hz" only, always set Pr. 3 Base frequency
to "50Hz". Leaving the base frequency unchanged from "60Hz" may make the voltage low and the torque insufficient. It
may result in an inverter trip (E.OC…) due to overload.
Parameter 
Number
Name
Initial Value
Setting Range
Description
3
Base frequency
60Hz
0 to 400Hz
Set the frequency when the motor 
rated torque is generated.
Changing example Change Pr. 3 Base frequency to 50Hz according to the motor rated frequency.
REMARKS
· Pr. 3 is invalid and Pr.84 Rated motor frequency is valid under Advanced magnetic flux vector control, Real sensorless vector
control, and vector control.
V/F
V/F
V/F
3.
Press         to choose parameter 
     setting mode.
Flicker
 
··· 
Parameter setting complete!!
7.
Press         to set.
· 
By turning         , you can read another parameter.
· 
Press          to show the setting again.
· 
Press          twice to show the next parameter.
4.
Turn          until 
Pr. 3 Base frequency 
     appears.
1.
Screen at power-ON
     The monitor display appears.
2.
Press         to choose the PU operation 
     mode.
PU indicator is lit.
Display
Operation
The parameter 
number 
read previously 
appears.
5.
Press         to show the currently set 
     value. (60Hz)
6.
Turn          to change it to
     the set value "         ". (50Hz)