Start and stop using terminals (External 
operation)
4.5 Start and stop using terminals (External operation)
4.5.1
Setting the frequency by the operation panel (Pr. 79 = 3)
[Connection diagram]
POINT
From where is the frequency command given?
· Operation at the frequency set in the frequency setting mode of the operation panel 
· Give a frequency command by switch (multi-speed setting) 
→ Refer to 4.5.2 (Refer to page 94)
· Perform frequency setting by a voltage output device 
 Refer to 4.5.3 (Refer to page 96)
· Perform frequency setting by a current output device 
→ Refer to 4.5.5 (Refer to page 98)
POINT
· Switch ON the STF(STR) signal to give a start command.
· Use the operation panel (FR-DU07) (
) to give a frequency command.
· Set “3” (External/PU combined operation mode 1) in Pr. 79 Operation mode selection.
Operation example
Performing operation at 30Hz.
Operation panel
(FR-DU07)
SD
STF
STR
Forward rotation 
start
Reverse rotation 
start
Inverter
1.
Screen at power-ON
     The monitor display appears.
Display
Operation
3.
Press          to choose the parameter 
     setting mode.
4.
Turn        until              (
Pr. 79) appears.
Flicker ··· Parameter setting complete!!
7.
Press        to set.
5.
Press          to read the present set value.
     "    "(initial value) appears.
6.
Turn           to change it to the
     setting value "    ".
The parameter 
number read
previously appears.
2.
Press          to choose the PU 
     operation mode.
PU indicator is lit.
8. 
Mode/monitor check 
Press        twice to choose the 
monitor/frequency monitor. 
[PU] indicator and [EXT] indicator are lit.