Mitsubishi Electronics FR-V540-1.5K to 55K ユーザーズマニュアル

ページ / 232
103
Additional functions (Pr. 59)
P
A
RAMETERS
3
3.9 Additional functions (Pr. 59)
3.9.1
Remote setting function selection (Pr. 59 
)
(1) Pr. 59 = "1" or "2"
*External operation speed or PU operation speed other than multi-speed
(2)  Pr. 59 = "3"
*External operation speed or PU operation speed other than multi-speed
Even if the control panel is located away from the enclosure, you can use contact signals to perform 
continuous variable-speed operation, without using analog signals.
Parameter
Name
Factory 
Setting
Setting 
Range
Remarks
59
Remote setting 
function selection
0
0
Remote function not activated.
Extended 
mode
1
Remote function activated: Stored into E
2
PROM.
2
Remote function activated: Not stored into E
2
PROM.
3
Remote function activated: Not stored into E
2
PROM.
(Turn on STF (STR) to clear remote setting)
REMARKS
• By merely setting this parameter, you can use the acceleration, deceleration and setting clear functions of the motorized 
speed setter (FR-FK).
• When the remote function is used, the output speed of the inverter can be compensated for as follows:
 
For external operation, speed set by RH/RM operation plus external analog speed command
 
For PU operation mode, speed set by RH/RM operation plus DU/PU digital setting speed
• When any value other than 0 is set in Pr. 59, multi-speed operation is invalid. (Refer to page 77.)
• Speed compensation by terminal 1 is made invalid when speed command by terminal 2 is selected.
 
Set "1" in Pr. 28 "multi-speed input compensation" to enable speed compensation of terminal 1 (Pr. 28 = "0").
speed
torque
Deceleration (RM)
Clear (RL)
Acceleration (RH)
Forward rotation (STF)
ON
ON
Power
ON
ON
ON
ON
ON
ON
Pr. 59 = "1"
Pr. 59 = "2"
ON
ON
ON
O
u
tput
 sp
ee
d (r
/m
in
)
*
ON
ON
ON
ON
ON
Deceleration (RM)
Acceleration (RH)
Forward rotation (STF)
Power
O
u
tput
 sp
ee
d (r
/m
in
)
*