Main circuit terminal specifications
1.2 Main circuit terminal specifications
Terminal Symbol
Terminal Name
Description
R, S, T
AC power input
Connect to the commercial power supply.
Keep these terminals open when using the high power factor converter (FR-
HC) or power regeneration common converter (FR-CV).
U, V, W
Inverter output
Connect a three-phase squirrel-cage motor or Mitsubishi dedicated motor.
R1, S1
Power supply for 
control circuit
Connected to the AC power supply terminals R and S. To retain the alarm 
display and alarm output or when using the high power factor converter (FR-
HC) or power regeneration common converter (FR-CV), remove the jumpers 
from terminals R-R1 and S-S1 and apply external power to these terminals.
Do not turn off the power supply for control circuit (R1, S1) with the main 
circuit power (R, S, T) on. Doing so may damage the inverter. The circuit 
should be configured so that the main circuit power (R, S, T) is also turned off 
when the power supply for control circuit (R1, S1) is off.
15K or less: 60VA, 18.5K to 55K: 80VA
P, PR
Brake resistor 
connection
Disconnect the jumper from terminals PR-PX (5.5K or less) and connect the 
optional brake resistor (FR-ABR) across terminals P-PR.
For the 15K or less, connecting the resistor further provides regenerative 
braking power.
P, N
Brake unit 
connection
Connect the optional FR-BU type brake unit, BU type brake unit, power 
regeneration common converter (FR-CV) or high power factor converter 
 
(FR-HC).
P, P1
DC reactor 
connection
Disconnect the jumper from terminals P-P1 and connect the optional DC 
reactor (FR-HEL/BEL).
PR, PX
Built-in brake circuit 
connection
When the jumper is connected across terminals PX-PR (factory setting), 
 
the built-in brake circuit is valid. (Provided for the 5.5K or less.)
Earth (Ground)
For earthing (grounding) the inverter chassis. Must be earthed (grounded).
CAUTION
• The inverter will be damaged if power is applied to the inverter output terminals (U, V, W). Never 
perform such wiring.
• When connecting the dedicated external brake resistor (FR-ABR), remove jumpers across terminals 
PR-PX (5.5K or less).
• When connecting the brake unit (FR-BU, BU type), remove jumpers across terminals PR-PX (5.5K or 
less). Refer to page 5, 6.