139
PID control (Pr. 128 to Pr. 134)
P
A
RAMETERS
3
3.14.2 E
2
PROM write selection (Pr. 342)
You can select either E
2
PROM or RAM to which parameters to be written during computer link communication 
operation (RS-485 communication by PU connector) and operation with a communication option. When changing 
the parameter values frequently, write them to the RAM (Pr. 342 = 1).
3.15 PID control (Pr. 128 to Pr. 134)
3.15.1 PID control (Pr. 128 to Pr. 134
)
<Setting>
(1) Basic PID control configuration
Parameter
Name
Factory Setting
Setting Value
342
E
2
PROM write selection
0
0
Write into E
2
PROM
1
Write into RAM
REMARKS
When the parameter setting is " not written to E
2
PROM" (setting = 1), the settings return to the original values (values saved in 
the E
2
PROM) at power on reset or terminal reset.
Pr. 342 Setting
0
(factory setting)
E
2
PROM write
Powering off the inverter will not erase the changed parameter values.
1
RAM write
Powering off the inverter will erase the changed parameter values. Therefore, the parameter 
values available when power is switched on again are the values stored in E
2
PROM last time.
The inverter can be used to exercise process control, e.g. flow rate, air volume or pressure.
z The voltage input signal (0 to ±10V) is used as a feedback value to constitute a feedback system for PID control.
Parameter 
Number
Name
Factory 
Setting
Setting Range
Remarks
128
PID action selection
10
10, 11, 30, 31
129
PID proportional band
100%
0.1 to 1000%, 9999
9999: No proportional control
130
PID integral time
1s
0.1 to 3600s, 9999
9999: No integral control
131
Upper limit
9999
0 to 100%, 9999
9999: Function invalid
132
Lower limit
9999
0 to 100%, 9999
9999: Function invalid
133
PID action set point for 
PU operation
0%
0 to 100%
134
PID differential time
9999
0.01 to 10.00s, 9999
9999: No differential control
speed
Kp
PID 
operation
1 +
Ti·S
1 + Td·S
x
Deviation
Process
value
fi
Manipulated
variable
Drive
circuit
Motor
IM
Kp: Proportional constant    Ti: Integral time    S: Operator    Td: Differential time
Set 
point
Inverter
Terminal 1
Pr.128 = 10, 11
x
Deviation
Process value
fi
Manipulated
variable
IM
Set 
point
Terminal 2
Pr.128 = 30, 31
+
-
Drive
circuit
Motor
Inverter
Kp
PID 
operation
1 +
Ti·S
1 + Td·S
Terminal 1