Mitsubishi Electronics FR-V540-1.5K to 55K ユーザーズマニュアル

ページ / 232
159
Orientation (Pr. 350 to Pr. 362, Pr. 393 to Pr. 399)
P
A
RAMETERS
3
3.27 Orientation (Pr. 350 to Pr. 362, Pr. 393 to Pr. 399)
3.27.1 Orientation control (Pr. 350, Pr. 351, Pr. 356, Pr. 357, Pr. 360 to Pr. 362, Pr. 393,
 
 Pr. 396 to Pr. 399
)
<Settings>
If the orientation command signal (X22) is turned on during operation after the various parameters have been set, 
the speed will decelerate to the "orientation switchover speed". After the "orientation stop distance" is calculated, 
the speed will further decelerate, and the "orientation state" (servo lock) will be entered. The "orientation complete 
signal" (ORA) will be output when the "orientation complete width" is entered.
(1) Setting I/O singals
Orientation is a function that stops a motor shaft at a position set by parameter using the motor built-in 
position detector (encoder). Install the option (FR-V5AM or FR-A5AP) on the inverter to perform stop position 
command control with a position detector (encoder) fitted to the machine. Refer to the instruction mannual of 
the option for details.
Pr. 350 "stop position command selection" is factory-set to "9999" to make the orientation control function 
invalid.
Parameter No.
Name
Setting Range
Factory Setting
Remarks
350
Stop position command selection
0, 1, 2, 3, 9999
9999
Extended mode
351
Orientation switchover speed
0 to 1000r/min
200r/min
356
Internal stop position command
0 to 16383
0
357
Orientation in-position zone
0 to 8192
11
360
External position command 
selection
0, 1, 2 to 127
0
361
Position shift
0 to 16383
0
362
Orientation position loop gain
0.1 to 100
10
393
Orientation selection
1, 2, 10, 11, 12
0
396
Orientation speed gain (P term)
0 to 1000%
60%
397
Orientation speed integral time
0 to 20.0s
0.333s
398
Orientation speed gain (D term)
0 to 100.0%
1%
399
Orientation deceleration ratio
0 to 1000
20
REMARKS
Check the Pr. 851 and Pr. 852 settings. (Refer to the Insruction Manual (basic).)
Input
Orientation command
X22 signal
Orientation control is valid with the signal on.
 
Set "22"
 
in any of Pr. 180 to Pr.183 or Pr. 187 (input 
terminal function selection). (Refer to page 150.)
Output
Orientaiton complete signal
ORA signal
Switched low if the orientation has stopped within the 
in-position zone while the start and orientation signals 
are input.
Open collector output
Permissible load 24VDC, 0.1A
Set 27 in any of Pr.190 to Pr. 192 or Pr. 195 (output 
terminal function selection).
(Refer to page 152.)
speed