Mitsubishi Electronics FR-V540-1.5K to 55K ユーザーズマニュアル

ページ / 232
182
Additional functions (Pr. 851 to Pr. 865)
3.34.5 Torque detection (Pr. 864
)
3.34.6 Low speed detection (Pr. 865
)
This function outputs a signal if the motor torque rises to or above the Pr. 864 setting.
The signal is used as operation and open signal for an electromagnetic brake.
Parameter
Name
Factory Setting
Setting Range
Remarks
864
Torque detection
150%
0 to 400%
Extended mode
The signal turns on when the output torque rises 
to or above the detection torque value set in Pr. 
864.
It turns off when the torque falls below the 
detection torque value.
Related parameters
TU signal terminal assignment 
⇒ Set "35" in any of Pr. 190 to Pr. 192 and Pr. 195 (output terminal function selection).  
(Refer to page 152.)
This function outputs a signal if the speed falls to or below the Pr. 865 setting.
Parameter
Name
Factory Setting
Setting Range
Remarks
865
Low speed detection
45r/min
0 to 3600r/min
Extended mode
<Operation>
The signal is output during inverter operation under the 
following conditions.
(1) Vector control
Motor speed 
≤ Pr. 865 ... ON
Motor speed 
> Pr. 865 ... OFF
(2) V/F control
Output speed 
≤ Pr. 865 speed equivalent ... ON
Output speed 
> Pr. 865 speed equivalent ... OFF
REMARKS
When 
"0" is set, low speed detection (LS signal) is output under position control only.
Related parameters
 LS signal terminal assignment 
⇒ Set "34" in any of Pr. 190 to Pr. 192 and Pr. 195 (output terminal function selection). 
 (Refer to page 152.)
Pr. 866
Refer to Pr. 55 (page 100)
speed
torque
position
O
utp
ut
 to
rq
ue
Torque detection
TU signal
ON
OFF
Pr.864
speed
torque
position
Low speed detection
LS signal
ON
OFF
Ou
tp
ut
 s
p
ee
d
Pr.865