Mitsubishi Electronics FR-V540-1.5K to 55K ユーザーズマニュアル

ページ / 232
40
Using the conventional motor and 
other motors
(3) Parameter setting
Parameters below are extended parameters. Set "1" in Pr. 160 "extended function selection" to read and make setting.
1.12.2 Precautions for and wiring of the motor with encoder (SF-JR with encoder)
• When the motor used is other than the dedicated motor, use the offline auto tuning function. (Refer to page 120
for details of offline auto tuning.)
• Set Pr. 800 to select the control method. (Refer to page 169.)
• To protect the motor from overheat, set electronic thermal relay function or provide an external thermal relay. 
(Refer to page 27.)
Parameter
Name
Factory Setting
Setting Range
Refer to
9
Electronic thermal O/L relay
0A
0 to 500A
71
Applied motor
30
0, 3 to 8, 10, 13 to 18, 20, 23, 24, 30, 33, 34
80
Motor capacity
Inverter capacity
0.4 to 55kW 
81
Number of motor poles
4
2, 4, 6
851
Number of encoder pulses
2048
0 to 4096
(Number of pulses before multiplied by 4)
Refer to the 
Instruction 
Manual (basic)
852
Encoder rotation direction
1
0, 1
CAUTION
• Pr. 71 setting
· SF-VR: "30"
· SF-JR (2, 4, 6P)- 2.2 to 55kW: "0"
 
SF-JR (4P)- 1.5kW or less: "20"
· SF-HRCA (4P): "10"
• When using motors other than the dedicated motor (SF-V5RU) or above motors, perform offline auto 
tuning. (Refer to page 120.)
Motor with encoder
CAUTION
• *Leave the unused terminals open.
• When not using an external thermal relay, set "0" in Pr. 876 "thermal relay protector input". Set Pr. 9 
"electronic thermal O/L relay".
• Check the power supply specification of encoder and change a jumper connector. (Refer to the 
Instruction Manual (basic).)
V
W
OH
SD
PA
PAR
PB
PBR
PZ
PZR
PG
SD
C
R
A
N
P
H
K
B
U
V
W
U
E
IM
Inverter
*
E
Motor with encoder
Encoder