Mitsubishi Electronics FR-HC2 ユーザーズマニュアル

ページ / 202
73
3
Parameter list
3.3 Parameter list
REMARKS
 indicates simple mode parameters.
The parameters shaded in 
 allow their settings to be changed during operation even if "1" (write disabled) is set to Pr. 77
Parameter write selection
Parameter
Name
Range
Increments
Initial 
value
Refer to 
page
Customer 
setting
 0
Simple mode selection
0, 9999
1
0
 1
Maximum power supply frequency
60Hz (Read only)
60Hz
 2
Minimum power supply frequency
50Hz (Read only)
50Hz
3
ROH terminal function selection
0 to 5, 9999
1
5
4
SOF terminal function selection
1
0
5
X1 terminal function selection
1
1
6
X2 terminal function selection
1
2
7
RES terminal function selection
1
3
8
SOF input selection
0, 1, 2
1
0
9
OH input selection
0, 1
1
0
10
RDY signal logic selection
0, 100
1
100
11
RSO terminal function selection
0 to 16, 98, 99, 100 to 116, 198, 
199, 9999
1
1
12
CVO terminal function selection
1
2
 13
Y1 terminal function selection
1
3
 14
Y2 terminal function selection
1
4
 15
Y3 terminal function selection
1
5
16
ABC terminal function selection
1
99
 22
Current limit level
0 to 220%
0.1%
150%
23
Current limit level (regenerative)
0 to 220%, 9999
0.1%
9999
24
OL signal output timer
0 to 25s, 9999
0.1
0
25
Input current detection level 
0 to 220%
0.1%
150%
26
Input current detection signal delay time
0 to 10s
0.1s
0s
27
Input current detection signal retention time 0 to 10s, 9999
0.1s
0.1s
28
Input current detection operation selection
0, 1
1
0
29
Zero current detection level
0 to 220%
0.1%
5%
30
Zero current detection time
0 to 1s
0.01s
0.5s
31
Life alarm status display
0 to 15 (Read only)
1
0
32
Inrush current limit circuit life display
0 to 100% (Read only)
1%
100%
33
Control circuit capacitor life display
0 to 100% (Read only)
1%
100%
34
Maintenance timer
0 (1 to 9998)
1
0
35
Maintenance timer alarm output set time
0 to 9998, 9999
1
9999
36
Cooling fan operation selection
0, 1
1
1
44
Instantaneous power failure detection signal 
clear
0, 9999
1
9999
45
AM output filter
0 to 5s
0.01s
0.01s
46
Watt-hour meter clear
0, 10, 9999
1
9999
47
Energization time carrying-over times
Read only
1
0
48
Cumulative power monitor digit shifted 
times
0 to 4, 9999
1
9999
49
Power supply frequency monitoring 
reference
45Hz to 65Hz
0.01Hz
60Hz
 50
AM terminal function selection
1 to 3, 5, 6, 7, 21, 1111 to 4444
1
1234
 51
Input power monitoring reference
0 to 100kW/0 to 3600kW
0.01kW/
0.1kW
Rated 
power
 52
DU/PU main display data selection
0, 5 to 10, 25, 1111 to 4444
1
1234
 53
Input voltage monitoring reference
0 to 500V
0.1V
220V/
440V
 54
FM terminal function selection
1 to 3, 5, 6, 7, 21, 1111 to 4444
1
1234
 55
Bus voltage monitoring reference
0 to 1000V
0.1V
340V/
680V
HC2.book  73 ページ  2012年11月19日 月曜日 午前10時52分