Mitsubishi Electronics FR-HC2 ユーザーズマニュアル

ページ / 202
77
3
Description of parameters
3.4.4
Operation selection of SOF signal and OH signal (Pr. 8, Pr. 9)
<SOF signal input status and Pr. 8 setting for the converter operation >
The converter does not operate at the Pr. 8 = "1" (NC contact) setting while FR-A7NC is not mounted. Set Pr. 8 = "2" (NC contact for external signals, NO
contact for CC-Link communication).
<OH signal input status and Pr. 9 setting for the converter operation >
Operation of SOF signal can be changed by the Pr. 8 setting, and OH signal by the Pr. 9 setting.
Parameter
Number
Name
Initial 
Value
Setting 
Range
Description
8
SOF input selection
0
0
Turning the SOF signal ON stops the converter operation. 
(NO contact)
1
Turning the SOF signal OFF stops the converter operation. 
(NC contact)
2
External signal: NC contact
CC-Link communication: NO contact
9
OH input selection
0
0
Turning the OH signal ON trips the converter. (NO contact)
1
Turning the OH signal OFF trips the converter. (NC contact)
SOF Signal Input Status
Converter Operation
External 
terminal 
Virtual terminal 
for CC-Link 
communication
Pr. 8 = 0 (NO contact)
Pr. 8 = 1 (NC contact) 
Pr. 8 = 2 
(External terminal: NC contact)
(Virtual terminal at CC-Link 
communication: NO contact)
OFF
OFF
Operation continues
Operation stops
Operation stops
OFF
ON
Operation stops
Operation stops
Operation stops
ON
OFF
Operation stops
Operation stops
Operation continues
ON
ON
Operation stops
Operation continues
Operation stops
OH Signal Input Status 
(external terminal)
Converter Operation
Pr. 9 = 0
Pr. 9 = 1
ON
Trips
Operation continues
OFF
Operation continues
Trips
HC2.book  77 ページ  2012年11月19日 月曜日 午前10時52分