Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
105
Setting of acceleration/deceleration time
and acceleration/deceleration pattern
4
4.7.3
Acceleration/deceleration pattern (Pr. 29, Pr. 140 to Pr. 143)
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 190)
...
Specifications differ according to the date assembled.  Refer to page 400 to check the SERIAL number.
You can set the acceleration/deceleration pattern suitable for application.
You can also set the backlash measures that stop acceleration/deceleration once at the parameter-set
frequency and time during acceleration/deceleration.
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
29
Acceleration/deceleration pattern 
selection
0
0
Linear acceleration/ deceleration
1
S-pattern acceleration/deceleration A
2
S-pattern acceleration/deceleration B
3
Backlash measures
6
Variable-torque acceleration/
deceleration
140
Backlash acceleration stopping frequency
1Hz
0 to 400Hz
Set the stopping frequency and time 
for backlash measures.
Valid when Pr. 29 = 3
141
Backlash acceleration stopping time
0.5s
0 to 360s
142
Backlash deceleration stopping frequency
1Hz
0 to 400Hz
143
Backlash deceleration stopping time
0.5s
0 to 360s
(1) Linear acceleration/ deceleration (Pr. 29 = "0", initial value)
⋅ When the frequency is changed for acceleration, deceleration, etc. in inverter
operation, the output frequency is changed linearly (linear acceleration/
deceleration) to reach the set frequency without straining the motor and
inverter. Linear acceleration/deceleration has a uniform frequency/time slope.
(2) S-pattern acceleration/deceleration A (Pr. 29 = "1")
⋅ For machine tool spindle applications, etc.
Used when acceleration/deceleration must be made in a short time to a high-
speed range of not lower than the base frequency. In this acceleration/
deceleration pattern, Pr. 3 Base frequency (fb) is the inflection point of the S
pattern and you can set the acceleration/deceleration time appropriate for motor
torque reduction in a constant-power operation range of base frequency (fb) or
higher.
CAUTION
⋅ As the acceleration/deceleration time of S-pattern acceleration/deceleration A, set the time taken until Pr. 3 Base frequency
is reached, not Pr. 20 Acceleration/deceleration reference frequency.
Setting value "0"
[Linear acceleration
/ deceleration]
Output frequency 
(Hz)
Time
fb
Output frequency 
(Hz)
Setting value "1"
Time
[S-pattern acceleration