Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
125
Function assignment of external
terminal and control
4
4.10.3 Condition selection of function validity by the second function selection 
signal (RT) (RT signal, Pr. 155)
⋅ When the RT signal turns ON, the second function becomes valid.
⋅ The second function has the following applications.
(a) Switching between normal use and emergency use
(b) Switching between heavy load and light load
(c) Changing of acceleration/deceleration time by broken line acceleration/deceleration
(d) Switching of characteristic between main motor and sub motor
⋅ When the RT signal is ON, the following second functions are selected at the same time.
You can select the second function using the external terminal (RT signal).
You can also set the RT signal operation condition (reflection time).
Parameter 
Number
Name
Initial Value
Setting Range
Description
155
RT signal function validity 
condition selection
0
0
Second function is immediately valid with ON of the 
RT signal.
10
Second function is valid only during the RT signal is 
ON and constant speed operation. 
(invalid during acceleration/deceleration)
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 190)
Second function 
connection diagram
Second acceleration/deceleration time example
Function
First Function Parameter 
Number
Second Function 
Parameter Number
Refer to 
Page
Torque boost
Pr. 0
Pr. 46
Base Frequency
Pr. 3
Pr. 47
Acceleration time
Pr. 7
Pr. 44
Deceleration time
Pr. 8
Pr. 44, Pr. 45
Electronic thermal relay function
Pr.  9
Pr. 51
Stall prevention
Pr. 22
Pr. 48, Pr. 49
Output frequency detection
Pr. 42(Pr. 43)
Pr. 50
PID control
Pr. 127 to Pr. 130, Pr. 133, 
Pr. 134, Pr. 760 to Pr. 764
Pr. 753 to Pr. 758,
Pr. 765 to Pr. 769
REMARKS
⋅ The RT signal is assigned to the RT terminal in the initial setting. By setting "3" in any of Pr. 178 to Pr. 189 (input terminal function
selection), the RT signal can be assigned to the other terminal.
CAUTION
⋅ Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Please
set parameters after confirming the function of each terminal.
♦ Parameters referred to 
Pr. 178 to Pr.189 (input terminal function selection)  
STF(STR)
Inverter
Start
Second 
function 
selection
RT
High speed
RH
Middle speed
RM
SD
(initial value)
RT
Output frequency
Setting value "0"
RH
RM
Acceleration 
time is reflected
Time