Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
151
4
4.11.5 How to calibrate the terminal CA when using the operation panel (FR-DU07)
REMARKS
⋅ Calibration can also be made for external operation. Set the frequency in External operation mode, and make calibration in
the above procedure.
⋅ Calibration is available even during operation.
⋅ For the operating procedure using the parameter unit (FR-PU04/FR-PU07), refer to the parameter unit instruction manual.
♦ Parameters referred to 
C0  CA terminal calibration  
C1  AM terminal calibration  
Press        to return to the               indication (step 4).
9. 
Press        .   Setting is complete.
2. 
Press          to choose the parameter 
      setting mode.
Flicker...Parameter setting complete!!
Analog indicator
3. 
Turn         until             appears.
1.
Confirmation of the RUN indication and 
     operation mode indication
4. 
Press         to display              .
6.
 Press          to enable setting.
7. 
If the inverter is at a stop, (press
              or         ) to start the inverter.
      (Motor needs not be connected.)
8.
 Turn          to adjust the indicator needle 
      to the desired position.
(    )
Turn         to read another parameter.
+
-
The parameter 
number read 
previously appears.
(When 
Pr. 54 = 1)
Press        twice to show the next parameter (             ).
Display
Operation
5.
Turn          until                appears.
    Set to
C0 CA terminal calibration.
C0 to C11 
setting 
is enabled.
The monitor set to 
Pr. 54 CA terminal 
function selection is displayed.