Energy saving operation and energy saving monitor
4.14.2 Energy saving monitor (Pr. 891 to Pr. 899)
From the power consumption estimated value during commercial power supply operation, the energy saving
effect by use of the inverter can be monitored/output.
Parameter 
Number
Name
Initial Value
Setting Range
200V class (400V class)
Description
52
DU/PU main display data 
selection
0
(output 
frequency)
0, 5, 6, 8 to 14, 17, 20, 
23 to 25, 50 to 57, 67, 
81 to 86, 100 
50: Power saving monitor
51: Cumulative saving power monitor
54
CA terminal function 
selection
1
(output 
frequency)
1 to 3, 5, 6, 8 to 14, 17, 21, 
24, 50, 52, 53, 67, 70, 85
50: Power saving monitor
158
AM terminal function 
selection
1 to 3, 5, 6, 8 to 14, 17, 21, 
24, 50, 52, 53, 67, 70, 86
891
Cumulative power monitor 
digit shifted times
9999
0 to 4
Set the number of times to shift the 
cumulative power monitor digit
Clamps the monitor value at 
maximum.
9999
No shift
Clears the monitor value when it 
exceeds the maximum value.
892
Load factor
100%
30 to 150%
Set the load factor for commercial 
power supply operation. Multiplied by 
the power consumption rate (page 167) 
during commercial power supply 
operation.
893
Energy saving monitor 
reference (motor capacity)
SLD/LD value 
of Applied 
motor Capacity
02330 
(01160) or 
less
0.1 to 55kW
Set the motor capacity (pump 
capacity). Set when calculating power 
saving rate, power saving rate average 
value, commercial operation power.
03160 
(01800) or 
more
0 to 3600kW
894
Control selection during 
commercial power-supply 
operation
0
0
Discharge damper control (fan)
1
Inlet damper control (fan)
2
Valve control (pump)
3
Commercial power-supply drive (fixed 
value)
895
Power saving rate 
reference value
9999
0
Consider the value during commercial 
power-supply operation as 100%
1
Consider the Pr. 893 setting as 100%.
9999
No function
896
Power unit cost
9999
 0 to 500
Set the power unit cost. Displays the 
power saving amount charge on the 
energy saving monitor.
9999
No function
897
Power saving monitor 
average time
9999
0
Average for 30 minutes
1 to 1000h
Average for the set time
9999
No function
898
Power saving cumulative 
monitor clear
9999
0
Cumulative monitor value clear
1
Cumulative monitor value hold
10
Accumulation continued
(communication data upper limit 9999)
9999
Accumulation continued
(communication data upper limit 
65535)
899
Operation time rate 
(estimated value)
9999
 0 to 100%
Use for calculation of annual power 
saving amount. Set the annual 
operation ratio (consider 365 days 
× 
24hr as 100%).
9999
No function
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 190)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write 
selection
.