Misoperation prevention and parameter 
setting restriction
4.17 Misoperation prevention and parameter setting restriction
4.17.1 Reset selection/disconnected PU detection/PU stop selection (Pr. 75)
Purpose
Parameter that must be Set
Refer to 
Page
Limit reset function
Trips stop when PU is disconnected
Stop from PU
Reset selection/disconnected 
PU detection/PU stop selection
Pr. 75
Prevention of parameter rewrite
Parameter write  selection
Pr. 77
Prevention of reverse rotation of the 
motor
Reverse rotation prevention 
selection
Pr. 78
Display necessary parameters
Display of applied parameters 
and user group function
Pr. 160, Pr. 172 to Pr. 174
Parameter restriction with using 
password
Password function
Pr. 296, Pr. 297
Control of parameter write by 
communication
EEPROM write selection
Pr. 342
You can select the reset input acceptance, disconnected PU (FR-DU07/FR-PU04/FR-PU07) connector detection
function and PU stop function.
Parameter 
Number
Name
Initial 
Value
Setting Range
200V class (400V class)
Description
75 *
Reset selection/disconnected 
PU detection/PU stop selection
14
02330 
(01160) 
or less
 0 to 3, 14 to 17
For the initial value, reset always enabled, 
without disconnected PU detection, and 
with PU stop function are set.
03160 
(01800) 
or more
 0 to 3, 14 to 17, 
100 to 103, 
114 to117
⋅The above parameter can be set when Pr. 160 User group read selection = "0". (Refer to page 190)
⋅The Pr. 75 value can be set any time. Also, if parameter (all) clear is executed, this setting will not return to the initial value.
* The above parameter allows its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter
write selection.
Pr. 75
Setting
Reset Selection
Disconnected PU 
Detection
PU Stop Selection
Reset Limit
(FR-F720-03160 
(FR-F740-01800) 
or more)
0
Reset input always enabled
If the PU is disconnected, 
operation will be continued.
Pressing  
decelerates 
the motor to a stop only in 
the PU operation mode.
Not function
1
Reset input enabled only when the 
inverter trips
2
Reset input always enabled
When the PU is 
disconnected, the inverter 
trips.
3
Reset input enabled only when the 
inverter trips
14
(initial 
value)
Reset input always enabled
If the PU is disconnected, 
operation will be continued.
Pressing  
decelerates 
the motor to a stop in any of 
the PU, External and 
Network operation modes.
15
Reset input enabled only when the 
inverter trips
16
Reset input always enabled
When the PU is 
disconnected, the inverter 
trips.
17
Reset input enabled only when the 
inverter trips
100
Reset input always enabled
If the PU is disconnected, 
operation will be continued.
Pressing  
decelerates 
the motor to a stop only in 
the PU operation mode.
Function
101
Reset input enabled only when the 
inverter trips
102
Reset input always enabled
When the PU is 
disconnected, the inverter 
trips.
103
Reset input enabled only when the 
inverter trips
114
Reset input always enabled
If the PU is disconnected, 
operation will be continued.
Pressing  
decelerates 
the motor to a stop in any of 
the PU, External and 
Network operation modes.
115
Reset input enabled only when the 
inverter trips
116
Reset input always enabled
When the PU is 
disconnected, the inverter 
trips.
117
Reset input enabled only when the 
inverter trips