Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
192
Misoperation prevention and parameter 
4.17.5 Password function (Pr. 296, Pr. 297)
The above parameters can be set when Pr. 160 User group read selection = "0".
When Pr. 296 
≠ "9999" (with password lock), note that Pr. 297 is always available for setting regardless of Pr. 160 setting.
* "0 or 9999" can be set to Pr. 297 at any time although the setting is invalid (the displayed value does not change).
....
Specifications differ according to the date assembled.  Refer to page 400 to check the SERIAL number.
(1) Parameter reading/writing restriction level (Pr. 296 )
Level of reading/writing restriction by PU/NET mode operation command can be selected by Pr. 296.
*1
If the parameter reading is restricted by the Pr. 160 setting, those parameters are unavailable for reading even when " " is indicated.
*2
If the parameter writing is restricted by the Pr. 77 setting, those parameters are unavailable for writing even when " " is indicated.
*3
Parameter access from unit where parameter is written in PU operation mode (initially set to operation panel (FR-DU07), parameter unit) is
restricted. (Refer to page 204 for PU mode operation command source selection) 
*4
This restricts parameter access from the command source that can write a parameter under Network operation mode (initially RS-485 terminal or
a communication option). (Refer to page 204 for NET mode command source.)
*5
Read/write is enabled only in the simple mode parameters registered in the user group when Pr.160 User group read selection = "9999". Pr.296 and
Pr.297 are always read/write enabled whether registered to a user group or not.
*6
If a communication option is installed, option fault (E.OPT) occurs, and inverter trips. (Refer to page 342.)
Registering 4-digit password can restrict parameter reading/writing.
Parameter 
Number
Name
Initial Value
Setting Range
Description
296
Password lock level
9999
0 to 6, 99, 100 to 
106, 199
Select restriction level of parameter reading/
writing when a password is registered.
9999
No password lock
297
Password lock/unlock
9999
1000 to 9998
Register a 4-digit password
(0 to 5) *
Displays password unlock error count.
(Reading only) 
(Valid when Pr. 296 = "100" to "106")
9999 *
No password lock
Pr. 296 Setting
PU Mode Operation Command
 
NET Mode Operation Command
RS-485 Terminal
Communication Option
Read
Write
Read
Write
Read
Write
9999
0, 100
×
×
×
×
×
×
1, 101
×
×
×
2, 102
×
3, 103
×
×
4, 104
×
×
×
×
×
5, 105
×
×
6, 106
×
×
×
99, 199
Only parameters registered in the user group can be read/written. *5
(For the parameters not registered in the user group, same restriction level as "4, 104" applies.)
: enabled, 
×: restricted