Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
261
PID control
4
4.20 PID control
4.20.1 Outline of PID control (Pr. 127 to Pr. 134, Pr. 241, Pr. 553, Pr. 554, 
Pr. 575 to Pr. 577)
Purpose
Parameter that must be Set
Refer 
to Page
Perform process control such as pump and 
air volume.
Outline of PID control
Pr. 127 to Pr. 134, Pr. 553, Pr. 554, 
Pr. 575 to Pr. 577
Calibrate the measured value input and PID 
display coefficient
Bias and gain calibration for 
PID displayed values
Pr. 241, Pr. 759, 
C42 (Pr. 934) to C45 (Pr. 935)
Drive a motor at a constant speed before 
starting to PID control
Pre-charge function
Pr. 760 to Pr. 769
Switch between two PID control settings
Second PID function
Pr. 753 to Pr. 758, Pr. 765 to Pr. 769
Pump function by multiple motors
Advanced PID function
Pr. 554, Pr. 575 to Pr. 591
The inverter can be used to exercise process control, e.g. flow rate, air volume or pressure.
The terminal 2 input signal or parameter setting is used as a set point and the terminal 4 input signal used as a
feedback value to constitute a feedback system for PID control.
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
127
PID control automatic 
switchover frequency
9999
 0 to 400Hz
Set the frequency at which the control is automatically 
changed to PID control.
9999
Without PID automatic switchover function
128
PID action selection
10
10, 110 
PID reverse action
Deviation value signal input
(terminal 1 
11, 111 
PID forward action
20, 120 
PID reverse action
Measured value (terminal 4 
Set point (terminal 2 
or Pr. 133)
21, 121 
PID forward action
50 
PID reverse action
Deviation value signal input
(L
ON
W
ORKS
, CC-Link, BACnet)
51 
PID forward action
60 
PID reverse action
Measured value, set point input
(L
ON
W
ORKS
, CC-Link, BACnet)
61 
PID forward action
70 
PID reverse action
Deviation value signal input
(PLC function)
71 
PID forward action
80 
PID reverse action
Measured value, set point input
(PLC function)
81 
PID forward action
90 
PID reverse action
Deviation value signal input
(PLC function)
(Not applied to the inverter frequency)
91 
PID forward action
100 
PID reverse action
Measured value, set point input
(PLC function)
(Not applied to the inverter frequency)
101 
PID forward action
129 
*1
PID proportional band
100%
0.1 to 1000%
If the proportional band is narrow (parameter setting is small), the
manipulated variable varies greatly with a slight change of the
measured value. Hence, as the proportional band narrows, the
response sensitivity (gain) improves but the stability deteriorates,
e.g. hunting occurs. 
Gain Kp = 1/proportional band
9999
No proportional control
PID integral time
1s
0.1 to 3600s
When deviation step is input, time (Ti) is the time required for 
integral (I) action to provide the same manipulated variable as 
proportional (P) action. 
As the integral time decreases, the set point is reached earlier but 
hunting occurs more easily.
9999
No integral control.
131
PID upper limit
9999
 0 to 100% 
Set the upper limit value. If the feedback value exceeds the 
setting, the FUP signal is output. The maximum input (20mA/5V/
10V) of the measured value (terminal 4) is equivalent to 100%.
9999
No function