Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
293
Special operation and frequency control
4
4.21 Special operation and frequency control
4.21.1 Bypass-inverter switchover function (Pr. 57, Pr. 58, Pr. 135 to Pr. 139, Pr. 159)
Purpose
Parameter that must be Set
Refer 
to Page
Switch between the inverter operation and 
bypass operation to operate.
Bypass-inverter switchover 
function
Pr. 57, Pr.58, Pr. 135 to Pr. 139, 
Pr. 159
Avoid overvoltage alarm due to regeneration by 
automatic adjustment of output frequency
Regeneration avoidance 
function
Pr. 665, Pr. 882 to Pr. 886
The complicated sequence circuit for bypass operation is built in the inverter. Hence, merely inputting the start,
stop or automatic switchover selection signal facilitates the interlock operation of the switchover magnetic
contactor.
Parameter 
Number
Name
Initial 
Value
Setting Range
200V class 
(400V class)
Description
57
Restart coasting time
9999
0
⋅ FR-F720-00077 (FR-F740-00038) or less ............ 0.5s,
⋅ FR-F720-00105 to 00340
(FR-F740-00052 to 00170) ................................... 1s,
⋅ FR-F720-00490 to 02330
(FR-F740-00250 to 01160).................................... 3.0s,
⋅ FR-F720-03160 (FR-F740-01800) or more........... 5.0s,
The above times are coasting time.
02330
(01160) 
or less
0.1 to 
5s
Set the waiting time for inverter-triggered restart after an 
instantaneous power failure.
03160
(01800) 
or more
0.1 to 
30s
9999
No restart
58
Restart cushion time
1s
0 to 60s
Set a voltage starting time at restart.
135
Electronic bypass sequence 
selection
0
0
Without electronic bypass sequence
1
With electronic bypass sequence
136
MC switchover interlock time
1s
 0 to 100s
Set the operation interlock time of MC2 and MC3.
137
Start waiting time
0.5s
 0 to 100s
Set the time slightly longer (0.3 to 0.5s or so) than the time
from when the ON signal enters MC3 until it actually turns ON.
138
Bypass selection at a fault
0
0
Inverter output is stopped (motor coast) at inverter fault.
1
Operation is automatically switched to bypass operation at 
inverter fault (Not switched when an external thermal relay 
operation (E.OHT) or CPU fault (E.CPU) occurs).
139
Automatic switchover 
frequency from inverter to 
bypass operation
9999
 0 to 60Hz
Set the frequency to switch inverter operation to bypass 
operation.
Inverter operation is performed from a start until Pr. 139 is 
reached, and when the output frequency is at or above Pr. 
139
, inverter operation is automatically switched to bypass 
operation.
9999
Without automatic switchover
159
Automatic switchover 
frequency range from bypass 
to inverter operation
9999
 0 to 10Hz
Valid during automatic switchover operation (Pr. 139 
≠ 9999)
When the frequency command decreases below (Pr. 139 - Pr. 
159
) after operation is switched from inverter operation to 
bypass operation, the inverter automatically switches 
operation to inverter operation and operates at the frequency 
of frequency command. When the inverter start command 
(STF/STR) is turned OFF, operation is switched to inverter 
operation also.
9999
Valid during automatic switchover operation (Pr. 139 
≠ 9999)
When the inverter start command (STF/STR) is turned OFF 
after operation is switched from inverter operation to bypass 
operation, operation is switched to inverter operation and the 
motor decelerates to stop.
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 190.)