4.21.2 Regeneration avoidance function (Pr. 665, Pr. 882 to Pr. 886)
(1) What is regeneration avoidance function? (Pr. 882, Pr. 883)
⋅ When the regeneration status is serious, the DC bus voltage rises and an overvoltage fault (E. OV ) may occur. 
When this bus voltage rise is detected and the bus voltage level reaches or exceeds Pr. 883, increasing the 
frequency avoids the regeneration status.
⋅ The regeneration avoidance operation, you can select whether it is always activated or activated only a constant speed.
⋅ Setting Pr. 882 to "1, 2" validates the regeneration avoidance function.
This function detects a regeneration status and increases the frequency to avoid the regeneration status.
Possible to avoid regeneration by automatically increasing the frequency and continue operation if the fan
happens to rotate faster than the set speed due to the effect of another fan in the same duct.
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
882
Regeneration 
avoidance operation 
selection
0
0
Regeneration avoidance function invalid
1
Regeneration avoidance function valid
2
Regeneration avoidance function is valid only during a constant 
speed operation
883
Regeneration 
avoidance operation 
level
380VDC/
760VDC *
300 to 800V
Set the bus voltage level at which regeneration avoidance 
operates. When the bus voltage level is set to low, overvoltage 
error will be less apt to occur. However, the actual deceleration 
time increases. The set value must be higher than the power 
supply voltage 
×  .
* The initial value differs according to the voltage level. (200V / 400V)
884
Regeneration 
avoidance at 
deceleration 
detection sensitivity 
0
0
Regeneration avoidance by bus voltage change ratio is invalid 
1 to 5
Set sensitivity to detect the bus voltage change ratio
Setting
1
5
Detection sensitivity low
high
885
Regeneration avoidance 
compensation 
frequency limit value
6Hz
 0 to 30Hz
Set the limit value of frequency which rises at activation of 
regeneration avoidance function.
9999
Frequency limit invalid
886
Regeneration avoidance 
voltage gain
100%
 0 to 200%
Adjust responsiveness at activation of regeneration avoidance. A 
larger setting will improve responsiveness to the bus voltage 
change. However, the output frequency could become unstable.  
When vibration is not suppressed by decreasing the Pr. 886 
setting, set a smaller value in Pr. 665.
665
Regeneration 
avoidance frequency 
gain
100%
 0 to 200%
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 190)
....
Specifications differ according to the date assembled.  Refer to page 400 to check the SERIAL number.
REMARKS
⋅ The inclination of the frequency increased or decreased by the regeneration avoidance function changes depending on the
regeneration status.
⋅ The DC bus voltage of the inverter is normally about 
 times greater than the input voltage.
When the input voltage is 220VAC, the bus voltage is about 311VDC.
When the input voltage is 440VAC, the bus voltage is about 622VDC.
However, it varies with the input power waveform.
⋅ The Pr. 883 setting should be kept higher than the DC bus voltage level. Otherwise, the regeneration avoidance function is
always ON even in the non-regeneration status and the frequency increases.
⋅ While overvoltage stall (
) is activated only during deceleration and stops the decrease in output frequency, the regeneration
avoidance function is always ON (Pr. 882 = 1) or activated only during a constant speed (Pr. 882 = 2) and increases the
frequency according to the regeneration amount.
⋅ Note that when coping parameters to the inverter without this function (inverter assembled in and before September 2005),
copied Pr.882 ="2" is regarded as Pr.882 ="0"(regeneration avoidance function invalid).
2
Pr.883
Time
Time
Regeneration avoidance operation 
example for acceleration
Bus voltage 
(VDC)
Output 
frequency(Hz)
During regeneration 
avoidance function operation
Pr.883
Time
Time
Regeneration avoidance operation 
example for constant speed
Bus voltage 
(VDC)
Output 
frequency(Hz)
During regeneration 
avoidance function operation
Pr.883
Time
Time
Bus voltage 
(VDC)
Output 
frequency(Hz)
During regeneration 
avoidance function operation
Regeneration avoidance operation 
example for deceleration