Useful functions
4
4.22.7 Setting multiple parameters as a batch (Pr.999) 
....
Specifications differ according to the date assembled.  Refer to page 400 to check the SERIAL number.
(1) Automatic parameter setting (Pr.999)
⋅Select which parameters to be automatically set, and set that to Pr. 999. Multiple parameter settings are changed
automatically. Refer to page 312 for the list of parameters that are changed automatically. 
⋅ Parameter settings are changed as a batch. Those include parameter settings for the extended PID display, the
Mitsubishi human machine interface (GOT) connection, rated frequency settings of 50Hz/60Hz, and
acceleration/deceleration time increment settings.
⋅ Multiple parameters are changed automatically. Users do not have to consider each parameter number.
(Parameter setting mode)
Parameter 
Number
Name
Initial value
Setting range
Description
999
Automatic parameter setting
9999
1
Normal PID setting
2
Extended PID setting
10
GOT initial setting (PU connector)
11
GOT initial setting (RS-485 terminals)
20
50Hz rated frequency
21
60Hz rated frequency
30
Acceleration/deceleration time 
(0.1s increment)
31
Acceleration/deceleration time 
(0.01s increment)
9999
No action
Pr.999 setting
Description
Operation in the parameter setting 
mode
1
Automatically applies the normal PID display settings in parameters
"AUTO" 
→ "PId" → Write "1"
2
Automatically applies the extended PID display settings in 
parameters
"AUTO" 
→ "PId" → Write "2"
10
Automatically sets the communication parameters for the GOT 
connection with a PU connector
"AUTO" 
→ "GOT" → Write "1"
11
Automatically sets the communication parameters for the GOT 
connection with RS-485 terminals
20
50Hz rated 
frequency
Sets the related parameters of the rated 
frequency according to the power supply 
frequency
"AUTO" 
→ "F50" → Write "1"
21
60Hz rated 
frequency
30
0.1s increment
Changes the setting increments of 
acceleration/deceleration time parameters 
without changing acceleration/deceleration 
settings
31
0.01s increment
"AUTO" 
→ "T0.01" → Write "1"
REMARKS