333
List of fault or alarm display
5
5.2 List of fault or alarm display
* If an error occurs when using the FR-PU04, "Fault 14" is displayed on
the FR-PU04.
...
Specifications differ according to the date assembled.  Refer to page 
400 
to check the SERIAL number.
Operation Panel 
Indication
Name
fault
Data 
code
Refer 
to
E
rro
r m
es
sa
ge
E---
Faults history
-
HOLD Operation panel lock
-
LOCd
Password locked
-
Er1 to 4 Parameter write error
-
rE1 to 4 Copy operation error
-
Err.
Error
-
Wa
rn
in
gs
OL
Stall prevention 
(overcurrent)
-
oL
Stall prevention 
(overvoltage)
-
RB
Regenerative brake 
prealarm
-
TH
Electronic thermal 
relay function prealarm
-
PS
PU stop
-
MT
Maintenance signal 
output
-
CP
Parameter copy
-
Ala
rm
FN
Fan alarm
-
Fa
ult
E.OC1 Overcurrent trip during 
acceleration
16
(H10)
E.OC2 Overcurrent trip during 
constant speed
17
(H11)
E.OC3 Overcurrent trip during 
deceleration or stop
18
(H12)
E.OV1
Regenerative 
overvoltage trip during 
acceleration
32
(H20)
E.OV2
Regenerative 
overvoltage trip during 
constant speed
33
(H21)
E.OV3
Regenerative 
overvoltage trip during 
deceleration or stop
34
(H22)
E.THT
Inverter overload trip
(electronic thermal 
relay function)
48
(H30)
E.THM
Motor overload trip
(electronic thermal 
relay function)
49
(H31)
E.FIN
Heatsink overheat
64
(H40)
E.IPF
Instantaneous power 
failure
80
(H50)
E.UVT Undervoltage
81
(H51)
E.ILF* Input phase loss
82
(H52)
E.OLT Stall prevention stop
96
(H60)
lt
E.GF
Output side earth 
(ground) fault overcurrent
128
(H80)
to
to
E.LF
Output phase loss
129
(H81)
E.OHT External thermal relay 
operation *2
144
(H90)
E.PTC* PTC thermistor 
operation
145
(H91)
E.OPT Option fault
160
(HA0)
E.OP1
E.OP2 Communication option 
fault
161
(HA1)
162
(HA2)
E. 1
E. 2
Option fault 
241
(HF1)
242
(HF2)
E.PE
Parameter storage 
device fault
176
(HB0)
E.PUE PU disconnection
177
(HB1)
E.RET Retry count excess
178
(HB2)
E.PE2* Parameter storage 
device fault
179
(HB3)
E. 5
E. 6
E. 7
E.CPU
CPU fault
245
(HF5)
246
(HF6)
247
(HF7)
192
(HC0)
E.CTE
Operation panel power 
supply short circuit, 
RS-485 terminal power 
supply short circuit
193
(HC1)
E.P24 24VDC power output 
short circuit
194
(HC2)
E.CDO* Output current detection 
value exceeded
196
(HC4)
E.IOH* Inrush current limit 
circuit fault
197
(HC5)
E.SER* Communication fault 
(inverter)
198
(HC6)
E.AIE* Analog input fault
199
(HC7)
E.PID* PID signal fault
230
(HE6)
E.BE
Brake transistor alarm 
detection/internal 
circuit fault 
112
(H70)
E.13
Internal circuit fault
253
(HFD)
E. PCH*
Pre-charge fault
229
(HE5)
E.LCI*
4mA input fault
228
(HE4)
Operation Panel 
Indication
Name
fault
Data 
code
Refer 
to