Mitsubishi Electronics FR-F700-NA ユーザーズマニュアル

ページ / 416
389
For customers who are replacing the conventional model with this inverter
(4) Main differences and compatibilities with the FR-F500(L) series
Appendix 1-2 Replacement of the FR-A100 <EXCELENT> series
Instructions for installation
• When using the installation holes of the FR-A100(E) series, FR-A5AT (intercompatibility attachment) is necessary.
Item
FR-F500(L)
FR-F700
C
h
ang
ed f
un
ct
io
ns
Simple mode 
parameters
61 parameters
20 parameters
User group
User group 1 (16), user group 2 (16)
(Pr. 160, Pr. 173 to Pr. 175)
User group (16) only
Setting methods were partially changed 
(Pr. 160, Pr. 172 to Pr. 173)
Communication 
option
Performing parameter clear and all clear (H5A96, 
HAA99) with the FR-A7ND clears Pr. 345 and Pr. 
346
.
Pr. 345 and Pr. 346 are not cleared.
Advanced PID 
(pump function)
Pr. 500 to Pr. 516
Parameter number change
Pr. 575 to Pr. 591
C
ha
nge
in
itia
l v
alu
e
Pr. 0 Torque 
boost 
Initial value
00250 to 00770: 2%, 00930, 01160: 1.5%
(When the torque boost value of the FR-F500 series 
used was the initial value, it is not necessary to change 
the torque boost value from the initial value when 
replacing with the FR-F700 series.)
D
el
e
te
d fu
nc
tio
n
s
User initial 
value setting 
(Pr. 199 )
Available
Not available
Substitutable with the copy function of the operation 
panel (FR-DU07)
Intelligent 
optimum 
acceleration/
deceleration
Available
(Pr. 60 setting "3" and Pr. 61 to Pr. 63)
Not available
For deceleration time, overvoltage fault can be avoided 
with regeneration avoidance function (Pr. 882 to Pr. 885).
Automatic 
torque boost
Pr. 38Pr. 39
Automatic torque boost was cleared because of addition 
of "Simple magnetic flux vector" (Pr. 80)
Terminal block
Removable terminal block
Removable terminal block
Upward compatibility (Terminal block of the F500 can be 
mounted)
PU
FR-PU04, DU04
FR-PU07
FR-DU07
FR-DU04 unavailable (Partly restricted when the FR-
PU04 is used. Refer to page 388.)
Plug-in option
Dedicated plug-in option (not compatible)
Computer link, relay output option
FR-A5NR
Built into the inverter
(RS-485 terminal, relay output 2 points)
Three boards can be mounted
Two board can be mounted
Installation size
FR-F720-00046, 00105, 00167, 00340, 00770, 00930, 01250, 01870, FR-F740-00023 to 00083, 00170, 
00470, 00770 to 01160 are compatible in mounting dimensions