Outback Power Systems GFX1312E ユーザーズマニュアル

ページ / 64
Specifications
 
900-0112-01-00 Rev B  
49
 
Table 19 
48-Volt Inverter Settings (MATE) 
Field Item  Default 
Minimum 
Maximum 
search sensitivity (see page 14 for increments) 
6 0  50 
search pulse length 
8 4  20 
Search
 
search pulse spacing 
60 AC cycles 
4 AC cycles 
120 AC cycles 
ac transfer control 
Grid 
Grid or Gen 
ac1/grid limit 
25 Aac 
2.5 Aac 
30 Aac 
Input
 
ac2/gen limit 
25 Aac 
2.5 Aac 
30 Aac 
low battery cut-out (LBCO) 
42 Vdc 
36 Vdc 
48 Vdc 
low battery cut-in (LBCI) 
50 Vdc 
40 Vdc 
56 Vdc 
Inverter
  
adjust output voltage 
230 Vac 
210 Vac 
250 Vac 
charger limit  
5.5 Aac 
0 Aac 
6 Aac 
absorb voltage 
57.6 Vdc 
52 Vdc 
64 Vdc 
absorb time limit 
1.0 hours 
0.0 hours 
24.0 hours 
float voltage 
54.4 Vdc 
48 Vdc 
60 Vdc 
float time period 
1.0 hours 
0.0 hours 
24.0 hours 
refloat voltage 
50 Vdc 
48 Vdc 
52 Vdc 
equalization voltage 
58.4 Vdc 
56 Vdc 
68 Vdc 
Charger 
 
 
 
equalization time period 
1.0 hours 
0.0 hours 
24.0 hours 
ac1/grid lower limit 
208 Vac 
140 Vac 
220 Vac 
ac1/grid upper limit 
252 Vac 
250 Vac 
280 Vac 
ac1/grid input limit 
25 Aac 
2.5 Aac 
30 Aac 
Grid 
ac1/grid transfer delay  
6 AC cycles 
0 AC cycles 
240 AC cycles 
gen input connect delay 
0.5 minutes 
0.2 minutes 
15 minutes 
ac2/gen lower limit 
208 Vac 
140 Vac 
220 Vac 
ac2/genupper limit 
252 Vac 
250 Vac 
280 Vac 
ac2/gen input limit 
25 Aac 
2.5 Aac 
30 Aac 
ac2/gen transfer delay  
6 AC cycles 
0 AC cycles 
240 AC cycles 
Generator 
(Gen)
 
ac2/gen support 
ON 
ON or OFF 
aux output control 
AUTO 
ONOFF, or AUTO 
aux output function 
Cool Fan 
Cool Fan, DivertDC, DivertAC, AC Drop, Vent 
Fan, Fault, GenAlert, LoadShed, or Remote 
genalert on voltage 
44 Vdc 
40 Vdc 
56 Vdc 
genalert on delay 
4 minutes 
0 minutes 
240 minutes 
genalert off set point 
56 Vdc 
48 Vdc 
72 Vdc 
genalert off delay 
9 minutes 
0 minutes 
240 minutes 
load shed off voltage 
44 Vdc 
40 Vdc 
56 Vdc 
vent fan on set point 
52 Vdc 
40 Vdc 
64 Vdc 
vent fan off period 
5 minutes 
0 minutes 
30 minutes 
diversion on voltage 
58.4 Vdc 
48 Vdc 
64 Vdc 
Auxiliary 
(AUX)
 
diversion off delay 
30 seconds 
0 seconds 
240 seconds 
Stacking
 
stack phase 
Master 
Master, OB Slave L1, 3p Classic B, 3p Classic C 
master adjust only 
0 0  7 
Power 
Save 
 
slave adjust only 
1 1  15 
sell re volts 
52 Vdc 
40 Vdc 
60 Vdc 
grid tie window 
User 
IEEE or User 
Sell
 
grid tie authority 
GridTie 
GridTie or No Sell 
vac input adjustment1
5
 
236 220  254 
vac output adjustment
5
 
236 220  254 
Calibration 
(Cal)
 
battery vdc adjustment2
6
 
2 0  4 
 
                                                               
5
  These values are in digital counts, not volts.  Lower counts stand for higher voltages, and higher counts mean lower voltages.  One count equals approximately 
1 Vac.  The range of adjustment is 15 Vac above nominal and 17 Vac below nominal. 
6
 These values are in digital counts, not volts.  One count equals 0.4 Vdc.  The range of adjustment is 0.8 Vdc above or below nominal.