Mitsubishi Electronics FR-F740P ユーザーズマニュアル

ページ / 410
4
Inverter and peripheral devices
1.2.1
Peripheral devices
Check the inverter model of the inverter you purchased. Appropriate peripheral devices must be selected according
to the capacity. Refer to the following list and prepare appropriate peripheral devices:
200V class
Motor 
Output (kW)
*1
Applicable Inverter 
Model
Moulded Case Circuit Breaker (MCCB) 
*2
 
or Earth Leakage Circuit Breaker (ELB) 
(NF or NV type)
Input Side Magnetic Contactor
*3
Power factor improving (AC or DC) reactor
Without
With
Without
With
0.75
FR-F720P-0.75K
10A
10A
S-N10
S-N10
1.5
FR-F720P-1.5K
15A
15A
S-N10
S-N10
2.2
FR-F720P-2.2K
20A
15A
S-N10
S-N10
3.7
FR-F720P-3.7K
30A
30A
S-N20, S-N21
S-N10
5.5
FR-F720P-5.5K
50A
40A
S-N25
S-N20, S-N21
7.5
FR-F720P-7.5K
60A
50A
S-N25
S-N25
11
FR-F720P-11K
75A
75A
S-N35
S-N35
15
FR-F720P-15K
125A
100A
S-N50
S-N50
18.5
FR-F720P-18.5K
150A
125A
S-N65
S-N50
22
FR-F720P-22K
175A
150A
S-N80
S-N65
30
FR-F720P-30K
225A
175A
S-N95
S-N80
37
FR-F720P-37K
250A
225A
S-N150
S-N125
45
FR-F720P-45K
300A
300A
S-N180
S-N150
55
FR-F720P-55K
400A
350A
S-N220
S-N180
75 FR-F720P-75K
400A
S-N300
90 FR-F720P-90K
400A
S-N300
110 FR-F720P-110K
500A
S-N400
*1
Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage of 200VAC 50Hz.
*2
Select the MCCB according to the power supply capacity.  
Install one MCCB per inverter.
For using commercial-power supply operation, select a breaker with capacity which allows the motor to be
directly power supplied.
For installation in the United States, Class RK5, Class J, Class CC, Class L, Class T or any faster acting
fuses or UL 489 Molded Case Circuit Breaker (MCCB) must be provided, in accordance with the National
Electrical Code and any applicable local codes.
For installation in Canada, Class RK5, Class J, Class CC, Class L, Class T or any faster acting fuses or UL
489 Molded Case Circuit Breaker (MCCB) must be provided, in accordance with the Canada Electrical
Code and any applicable provincial codes. (Refer to the Instruction Manual (basic).)
*3
Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the
MC with class AC-3 rated current for the motor rated current.
CAUTION
⋅ When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model, and select cable and reactor according to the motor output.
⋅ When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the
inverter, etc. Identify the cause of the trip, then remove the cause and power ON the breaker.