Function assignment of external 
4.11.5 Output terminal function selection (Pr. 190 to Pr. 196)
(1) Output signal list
⋅ You can set the functions of the output terminals.
⋅ Refer to the following table and set the parameters: (0 to 99: Positive logic, 100 to 199: Negative logic)
You can change the functions of the open collector output terminal and relay output terminal.
Parameter 
Number
Name
Initial 
Value
Initial Signal
Setting Range
190
RUN terminal 
function selection
Open 
collector 
output 
terminal
0
RUN (inverter running)
0 to 5, 7, 8, 10 to 19, 25, 26, 
45 to 48, 57, 64, 67, 70, 79, 85, 90 to 
96, 98, 99, 100 to 105, 107, 108, 110 
to 116, 125, 126, 145 to 148, 157, 
164, 167, 170, 179, 185, 190 to 
196, 198, 199, 9999
191
SU terminal function 
selection
1
SU (up to frequency)
192
IPF terminal function 
selection
2
IPF (instantaneous power 
failure, undervoltage)
193
OL terminal function 
selection
3
OL (overload alarm)
194
FU terminal function 
selection
4
FU (output frequency 
detection)
195
ABC1 terminal 
function selection
Relay 
output 
terminal
99
ALM (fault output)
0 to 5, 7, 8, 10 to 19, 25, 26, 45 to 
48, 57, 64, 67, 70, 79, 85, 90, 91, 
94 to 96, 98, 99, 100 to 105, 107, 
108, 110 to 116, 125, 126, 145 to 
148, 157, 164, 167, 170, 179, 185, 
190, 191, 194 to 196, 198, 199, 
9999
196
ABC2 terminal 
function selection
9999
No function
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 201)
Setting
Signal 
Name
Function
Operation
Related 
Parameters
Refer 
to Page
Positive 
Logic
Negative 
Logic
0
100
RUN
Inverter running
Output during operation when the inverter 
output frequency rises to or above Pr. 13 
Starting frequency
 (0.01Hz under IPM motor 
control).
1
101
SU
Up to frequency 
*1
Output when the output frequency is 
reached to the set frequency.
Pr. 41
2
102
IPF
Instantaneous power 
failure/undervoltage
Output at occurrence of an instantaneous 
power failure or when undervoltage 
protection is activated.
Pr. 57
3
103
OL
Overload warning
Output while stall prevention function is 
activated.
Pr. 22, Pr. 23, 
Pr. 66, Pr. 148, 
Pr. 149, Pr. 154
4
104
FU
Output frequency 
detection
Output when the output frequency reaches 
the frequency setting in Pr. 42 (Pr. 43 for 
reverse rotation).
Pr. 42, Pr. 43
5
105
FU2
Second output 
frequency detection
Output when the output frequency reaches 
the frequency setting in Pr. 50.
Pr. 50
7
107
RBP
Regenerative brake 
pre-alarm
Output when 85% of the regenerative brake 
duty set in Pr. 70 is reached.
Setting can be made for the 75K or higher.
Pr. 70
8
108
THP
Electronic thermal 
relay function 
prealarm
Output when the electronic thermal value 
reaches 85% of the trip level.
(Electronic thermal relay function protection 
(E.THT/E.THM) activates, when the value 
reached 100%.)
Pr. 9
10
110
PU
PU operation mode
Output when the PU operation mode is 
selected.
Pr. 79
11
111
RY
Inverter operation 
ready
Output when the reset process is completed 
(when the inverter can be started by 
switching the start signal ON or while it is 
running) after powering ON the inverter.
12
112
Y12
Output current 
detection
Output when the output current is higher 
than the Pr. 150 setting for longer than the 
time set in Pr. 151.
Pr. 150, Pr. 151