Mitsubishi Electronics FR-F740P ユーザーズマニュアル

ページ / 410
152
Monitor display and monitor output signal
4.12.2 DU/PU monitor display selection 
(Pr. 52, Pr. 54, Pr. 158, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564, Pr. 891)
(1) Monitor description list (Pr. 52)
⋅ Set the monitor to be displayed on the operation panel (FR-DU07) and parameter unit (FR-PU04/FR-PU07) in Pr.
52 DU/PU main display data selection.
⋅ Set the monitor to be output to the terminal FM(pulse train output) in Pr. 54 FM terminal function selection.
⋅ Set the monitor to be output to the terminal AM (analog output (0 to 10VDC voltage output)) in Pr. 158 AM terminal
function selection.
⋅ Refer to the following table and set the monitor to be displayed. (The signals marked × cannot be selected for
monitoring)
The monitor to be displayed on the main screen of the operation panel (FR-DU07)/parameter unit (FR-PU04/FR-
PU07) can be selected.
In addition, signals to be output from the terminal FM (pulse train output) and AM (analog voltage output) can be
selected.
Parameter 
Number
Name
Initial Value
Setting Range
Description
52*
DU/PU main display data 
selection
0
(output 
frequency)
0, 5, 6, 8 to 14, 
17, 20, 23 to 25, 
50 to 57, 100
Select the monitor to be displayed on the 
operation panel and parameter unit.
Refer to the following table for monitor description.
54*
FM terminal function 
selection
1
(output 
frequency)
1 to 3, 5, 6, 
8 to 14, 17, 21, 
24, 50, 52, 53
Select the monitor output to terminal FM.
158*
AM terminal function 
selection
Select the monitor output to terminal AM.
170
Watt-hour meter clear
9999
0
Set "0" to clear the watt-hour meter monitor.
10
Sets the maximum value for the monitoring from 
communication to 9999kWh.
9999
Sets the maximum value for the monitoring from 
communication to 65535kWh.
171
Operation hour meter clear
9999
0, 9999
Set "0" to clear the operation time monitor.
Setting "9999" has no effect.
268 *
Monitor decimal digits 
selection
9999
0
Displayed as integral value.
1
Displayed in 0.1 increments.
9999
No function
563
Energization time 
carrying-over times
0
0 to 65535
(reading only)
Displays the numbers of cumulative energization 
time monitor exceeded 65535h. Reading only
564
Operating time carrying-
over times
0
0 to 65535
(reading only)
Displays the numbers of operation time monitor 
exceeded 65535h. Reading only
891*
Cumulative power monitor 
digit shifted times
9999
0 to 4
Set the number of times to shift the cumulative 
power monitor digit.
Clamps the monitor value at maximum.
9999
No shift
Clears the monitor value when it exceeds the 
maximum value.
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 201)
* This parameter allows its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77
Parameter write selection.
Types of Monitor
Increments
Pr. 52 Parameter 
Setting Value
Pr. 54 (FM) 
Pr. 158 (AM) 
Parameter 
Setting 
Value
Full-scale value 
of the terminal 
FM and AM
Description
DU LED
PU main
monitor
Output frequency
0.01Hz
0/100
1
Pr. 55
Displays the inverter output frequency
Output current
0.01A/0.1A 
0/100
2
Pr. 56
Displays the inverter output current 
effective value
Output voltage
0.1V
0/100
3
200V class: 
400V
400V class: 
800V
Displays the inverter output voltage
Fault display
0/100
×
Displays 8 past faults individually
Frequency setting 
value
0.01Hz
5
5
Pr. 55
Displays the set frequency