4.13.4 Power failure-time deceleration-to-stop function (Pr. 261 to Pr. 266 )
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 201)
*1
When the setting of Pr. 21 Acceleration/deceleration time increments is "0" (initial value), the setting range is "0 to 3600s" and the setting increments
are "0.1s", and when the setting is "1", the setting range is "0 to 360s" and the setting increments are "0.01s"
*2
Performing IPM parameter initialization changes the settings. (Refer to page 80)
When a power failure or undervoltage occurs, the inverter can be decelerated to a stop or can be decelerated
and re-accelerated to the set frequency.
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
261
Power failure stop 
selection
0
Operation at 
undervoltage or 
power failure
At power restoration 
during power failure 
deceleration
Deceleration time to a 
stop
0
Coasts to a stop
Coasts to a stop
1
Decelerates to a stop
Decelerates to a stop
Depends on Pr. 262 to 
Pr. 266 settings
2
Decelerates to a stop
Accelerates again
Depends on Pr. 262 to 
Pr. 266 settings
21
Decelerates to a stop
Decelerates to a stop
Automatically adjusts 
the deceleration time
22
Decelerates to a stop
Accelerates again
Automatically adjusts 
the deceleration time
262
Subtracted frequency 
at deceleration start
3Hz
 0 to 20Hz
Normally operation can be performed with the initial value unchanged. But 
adjust the frequency according to the magnitude of the load specifications 
(moment of inertia, torque).
263
Subtraction starting 
frequency
60Hz
 0 to 
120Hz
When output frequency 
≥ Pr. 263
Decelerate from the speed obtained from output frequency minus Pr. 262.
When output frequency 
Pr. 263
 Decelerate from output frequency
9999
Decelerate from the speed obtained from output frequency minus Pr. 262.
264
Power-failure 
deceleration time 1
5s
 0 to 3600/ 
360s 
Set a deceleration slope down to the frequency set in Pr. 266.
265
Power-failure 
deceleration time 2
9999
 0 to 3600/ 
360s 
Set a deceleration slope below the frequency set in Pr. 266.
9999
Same slope as in Pr. 264
266
Power failure 
deceleration time 
switchover frequency
60Hz
 0 to 
400Hz
Set the frequency at which the deceleration slope is switched from the Pr. 264 
setting to the Pr. 265 setting.
(1) Connection and parameter setting
⋅ Remove the jumpers across terminals R/L1 and R1/L11 and
across terminals S/L2 and S1/L21, and connect terminals
R1/L11 and P/+ and terminals S1/L21 and N/-.
⋅ When setting of Pr. 261 is not "0", the motor decelerates to a
stop if an undervoltage, power failure or input phase loss
(when Pr. 872 ="1"(input phase loss enabled)) occurs.
(2) Operation outline of deceleration to stop at
power failure
⋅ If an undervoltage or power failure occurs, the output
frequency is dropped by the frequency set in Pr. 262 .
⋅ Deceleration is made in the deceleration time set in Pr. 264.
(The deceleration time setting is the time required from Pr. 20
Acceleration/deceleration reference frequency
 to a stop.)
⋅ Change the deceleration time (slope) to a stop using Pr.265
when the frequency is too low to obtain the regenerative
energy, or in other instances. 
⋅ With the Pr.261 = "21 or 22" setting, the deceleration time is
automatically adjusted to keep (DC bus) voltage constant in
the converter when the motor decelerates to a stop.
(The Pr.262 to Pr.266 settings become invalid.)
Power supply
Remove the jumper
Inverter
S/L2
T/L3
S1/L21
P/+
N/
R1/L11
R/L1
Connect terminal
R1/L11 and P/+
and terminal
S1/L21 and N/-.
Pr.264
Power-failure 
deceleration time 1
Pr.265
Power-failure 
deceleration 
time 2
Time
Power supply
Output
frequency
Subtracted
frequency at
deceleration start
Pr.262
Power-failure 
deceleration 
time switchover 
frequency
Pr.266