Mitsubishi Electronics FR-F740P ユーザーズマニュアル

ページ / 410
203
setting restriction
4
4.18.5 Password function (Pr. 296, Pr. 297)
*1
This parameter can be set when Pr. 160 User group read selection = "0".
*2
If Pr. 296 = "9999" (no password lock), Pr. 297 can be set while Pr. 160 = "0." When the password lock is valid, Pr. 297 can be set regardless of the
Pr. 160 setting.
*3
"0 or 9999" can be set to Pr.297 at any time although the setting is invalid (the displayed value does not change).
*4
This parameter allows its setting to be changed during operation in any operation mode even if "0 (initial value) or 1" is set in Pr. 77 Parameter write
selection
.
(1) Parameter reading/writing restriction level (Pr. 296 )
Level of reading/writing restriction by PU/Network(NET) mode operation command can be selected by Pr. 296.
*1
If the parameter reading is restricted by the Pr. 160 setting, those parameters are unavailable for reading even when " " is indicated.
*2
If the parameter writing is restricted by the Pr. 77 setting, those parameters are unavailable for writing even when " " is indicated.
*3
Parameter access from unit where parameter is written in PU operation mode (initially set to operation panel (FR-DU07), parameter unit) is
restricted. (Refer to page 219 for PU mode operation command source selection) 
*4
This restricts parameter access from the command source that can write a parameter under Network operation mode (initially RS-485 terminal or
a communication option). (Refer to page 219 for NET mode command source.)
*5
Read/write is enabled only in the simple mode parameters registered in the user group when Pr.160 User group read selection = "9999". Pr.296 and
Pr.297 are always read/write enabled whether registered to a user group or not.
*6
If a communication option is installed, option fault (E.OPT) occurs, and inverter trips. (Refer to page 318.)
Registering a 4-digit password can restrict parameter reading/writing.
Parameter 
Number
Name
Initial Value
Setting Range
Description
296
Password lock level
9999
0 to 6, 99, 100 to 
106, 199
Select restriction level of parameter reading/
writing when a password is registered.
9999
No password lock
297
Password lock/unlock
9999
1000 to 9998
Register a 4-digit password
(0 to 5) 
Displays password unlock error count.
(Reading only) 
(Valid when Pr. 296 = "100" to "106")
9999 
Password being unlocked
Pr. 296 Setting
PU Mode Operation Command
 
PU Mode Operation Command
Read
Write
Read
Write
RS-485 terminal
Communication 
option
Read
9999
0, 100
×
×
×
×
1, 101
×
×
2, 102
×
3, 103
×
4, 104
×
×
×
×
5, 105
×
×
6, 106
×
×
99, 199
Only the parameters registered in the user group can be read/written.
(For the parameters not registered in the user group, same restriction level as "4, 104" applies.)
: enabled, 
×: restricted