Selection of operation mode and 
operation location
4.19 Selection of operation mode and operation location
4.19.1 Operation mode selection (Pr. 79)
The above parameters can be changed during a stop in any operation mode.
*1
This parameter allows its setting to be changed in any operation mode even if "0 (initial value) or 1" is set in Pr. 77 Parameter write selection.
*2
The priorities of the frequency commands when Pr. 79 = "3" are "Multi-speed operation (RL/RM/RH/REX) > PID control (X14) > terminal 4 analog
input (AU) > digital input from the operation panel".
Purpose
Parameter that must be set
Refer to page
Operation mode selection
Operation mode selection
Pr. 79
Started in network operation mode
Operation mode at power ON
Pr. 79, Pr. 340
Selection of operation location
Selection of start command source, speed 
command source and operation location 
during communication operation
Pr. 338, Pr. 339, 
Pr. 550, Pr. 551
Used to select the operation mode of the inverter.
Mode can be changed as desired between operation using external command signals (external operation), operation
from the PU (FR-DU07/FR-PU04/FR-PU07), combined operation of PU operation and external operation (external/PU
combined operation, and network operation (when RS-485 terminals or a communication option is used).
Parameter Number
Name
Initial Value
Setting Range
79
Operation mode selection
0
0 to 4, 6, 7
POINT
• Use the easy setting mode to set Pr. 79 in simple steps.  (Refer to page 62)
Pr.79
Setting
Description
LED Indication
: OFF     
: ON
Refer 
to 
page
0
Use External/PU switchover mode 
Press 
 to switch between the PU and External operation mode. 
At power ON, the inverter is in the External operation mode.
PU operation mode
External operation mode
NET operation mode
1
Operation mode
Frequency command
Start command
PU operation mode
PU operation mode (fixed)
Setting by the operation 
panel (FR-DU07) and PU 
(FR-PU04/FR-PU07)
Input by 
 and 
 on 
PU (FR-DU07/FR-PU04/FR-
PU07)
2
External operation mode (fixed)
The operation can be performed 
by switching between the 
External and NET operation 
modes.
External signal input (from 
terminal 2, 4, and 1, JOG, 
multi-speed selection, etc.) 
External signal input (from 
terminal STF and STR)
External operation mode
NET operation mode
3
External/PU combined 
operation mode 1
PU (FR-DU07/FR-PU04/FR-
PU07) setting or external 
signal input (multi-speed 
setting, across terminals 4 
and 5 (valid when AU signal 
turns ON)). 
External signal input (from 
terminal STF and STR)
External/PU combined 
operation mode
4
External/PU combined 
operation mode 2
External signal input
(Terminal 2, 4, 1, JOG, multi-
speed selection, etc.)
Input by 
 and 
 on 
PU (FR-DU07/FR-PU04/FR-
PU07)
6
Switchover mode
Switch among PU operation, External operating, and NET operation while keeping the
same operating status.
PU operation mode
External operation mode
NET operation mode
7
External operation mode (PU operation interlock)
X12 signal ON: Operation mode can be switched to the PU operation mode.
(output stop during External operation)
X12 signal OFF: Operation mode cannot be switched to the PU operation mode.
REMARKS
If switching of the operation mode is invalid even though Pr. 79 is set, refer to 5.5.9 Operation mode is not changed properly (page 327).