Useful functions
4.22.7 Setting multiple parameters as a batch (Pr.999)
* This parameter allows its setting to be changed in any operation mode even if "0 (initial value)" is set in Pr. 77 Parameter write selection.
(1) Automatic parameter setting (Pr.999)
⋅ Select which parameters to be automatically set, and set that to Pr. 999. Multiple parameter settings are changed 
automatically. Refer to page 293 for the list of parameters that are changed automatically. 
⋅ Parameter settings are changed as a batch. Those include communication parameter settings for the
Mitsubishi human machine interface (GOT) connection, rated frequency settings of 50Hz/60Hz, and
acceleration/deceleration time increment settings.
⋅ Multiple parameters are changed automatically. Users do not have to consider each parameter number.
(Parameter setting mode)
Parameter 
Number
Name
Initial value
Setting range
Description
999 *
Automatic parameter setting
9999
10
GOT initial setting (PU connector)
11
GOT initial setting (RS485 terminals)
20
50Hz rated frequency
21
60Hz rated frequency
30
Acceleration/deceleration time 
(0.1s increment)
31
Acceleration/deceleration time 
(0.01s increment)
9999
No action
Pr.999 setting
Description
Operation in the parameter setting 
mode
10
Automatically sets the communication parameters for the GOT 
connection with a PU connector
"AUTO" 
→ "GOT" → Write "1"
11
Automatically sets the communication parameters for the GOT 
connection with RS-485 terminals
20
50Hz rated 
frequency
Sets the related parameters of the rated 
frequency according to the power supply 
frequency
"AUTO" 
→ "F50" → Write "1"
21
60Hz rated 
frequency
30
0.1s increment
Changes the setting increments of 
acceleration/deceleration time parameters 
without changing acceleration/deceleration 
settings
31
0.01s increment
"AUTO" 
→ "T0.01" → Write "1"
REMARKS
If the automatic setting is performed, the selected settings including the changed parameter settings will be changed.