Trane Tracer ユーザーズマニュアル

ページ / 32
4
Start-up
Procedure
Installation of New Units
1.
Follow all instruction for 
installation of water source 
heat pumps as detailed in the 
IOM (Installation Operation 
Maintenance manual).
2.
Disconnect power or disable 
the circuit breaker to unit.
3.
Run communication link wire to 
field terminal strips 14 and 16. 
(See wiring diagram in the 
unit).
4.
Install zone sensor to low 
voltage control terminals 1 
through 6. (See wiring diagram 
in the unit and zone sensor 
submittals).
5.
Verify that water connections 
have been made to unit, then 
ensure that water is circulating 
through the unit.
6.
Reapply power.
7.
Check for STATUS GREEN LED 
operation to ensure power and 
communication has been made 
to the ZN510
.
Peel IDENTIFICATION TAG from unit 
and place in the ZN510 IOP, on a 
copy of Sheet 6 of this document, or 
on building plans for future location 
use. The actual room location on the 
tag may be hand written.
Zone Sensor Placement
Zone sensor location is an important 
element of effective room control 
and comfort.
The best sensor location is typically 
on a wall, remote from the 
HVAC
 unit. 
Readings at this location assure that 
the desired setpoint is achieved 
across the space, not just near the 
unit itself. It may be necessary to 
subdivide the zone with multiple 
units to ensure adequate control 
and comfort.
The following are typical areas 
where the zone sensor should not 
be mounted:
z
Near drafts or “dead spots” 
(e.g., behind doors or corners)
z
Near hot or cold air ducts
z
Near radiant heat (e.g., heat 
emitted from appliances or the 
sun)
z
Near concealed pipes or 
chimneys
z
On outside walls or other non-
conditioned surfaces
z
In air flows from adjacent zones 
or other units