1
108
Table 28. Data Share Points.
User Address
NvName
Field Name
Engineering Units: English 
(Metric) or States plus Range
Di
gita
l S
tate
 or
 V
alu
e o
f St
ate
Default
E
-Vi
sion
 (M
, P
, S)
Sh
a
re
Map
 D
irect A
ccess
M
anu
al
 Co
nf
ig
.
F
ailu
re Det
ect
E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic
Comments
DestOaEnth
nviOdEnthS7
mA
4 to 20
SI_INVALID
X
X
X nviOdEnth allows one outdoor enthalpy sensor at a node to be shared by many 
other nodes. When nviOdEnth is not SI_INVALID then any local sensor is 
ignored by the local control algorithm and OdEnth is used instead. If the value is 
outside the allowed range (4 to 20 mA), then the node uses the value of the 
nearest range limit.
SrcOaEnth
nvoOdEnthS7
mA
4 to 20
SI_INVALID
M X
X
nvoOdEnth allows the local outdoor enthalpy sensor to be shared with other 
nodes and is typically bound to OdEnth on other nodes. If the local sensor is 
configured by Select, nviOdEnth is periodically sent on the network. If the local 
sensor is not configured or currently showing an error, the value is SI_INVALID.
SrcMonSwCt
nvoMonSw
value
0 to 100
0
X
MonSw value allows the monitor switch to be shared with another node. MonSw 
is typically bound to an SBC to indicate a user defined alarm condition. The 
output values have the following meanings: If the state is SW_OFF and the 
value is 0, then the monitor switch is open. If the state is SW_ON and the value 
is 100 percent, then the monitor switch is closed. If the state is SW_NUL and 
the value is 0, then the monitor switch is not configured by Select.
SrcMonSw
nvoMonSw
state
SW_OFF
SW_ON
SW_NUL
0
1
255
SW_NUL
M
X
For MonSw.state, refer to MonSw.value.
nviIaqOvr
value
0 to 100
0
IaqOvr allows an indoor air quality sensor to be shared by many other nodes. 
The states are follows: If the state is SW_OFF and the value is don’t care, then 
the indoor air quality is acceptable. If the state is SW_ON and the value is 0, 
then the indoor air quality is acceptable. If the node receives this combination of 
state and value, then state is set to SW_OFF. If the state is SW_ON and the 
value is not zero, then the indoor air quality is not acceptable and additional 
outdoor air is needed to bring it back to acceptable. If the state is SW_NUL and 
the value is don’t care, then the indoor air quality is acceptable. If the state is 
other, then the network variable is not bound, the communications path from the 
sending node has failed, or the sending node has failed. The indoor air quality is 
acceptable.
DestIaqOvrd
nviIaqOvr
state
SW_OFF
SW_ON
SW_NUL
0
1
255
SW_NUL
M X
X X
X For IaqOvr.state, refer to IaqOvr.value.
SrcIaqOvrCt
nvoIaqOvr
value
0 to 100
0
X X
IaqOvr allows an indoor air quality sensor to be shared with other nodes and is 
typically bound to IaqOvr on other nodes. If Data2.siSpaceCo2 is not 
SI_INVALID, and exceeds Aux1SetPt.CO2IaqLimit, then poor air quality is 
detected. In addition, if a local digital input is configured for IAQ_OVERRIDE_IN 
and IO.IaqOverRide is 1 (TRUE) then poor air quality is also detected. The state 
has the following meanings: If the state is SW_OFF and the value is 0, then the 
indoor air quality is acceptable. If the state is SW_ON and the value is 100 
percent, then the indoor air quality is not acceptable and additional outdoor air is 
needed to bring it back to an acceptable state. If the state is SW_NUL and the 
value is 0, then the economizer for this node has not been configured or there is 
no sensor (via IO.SpaceDo2 or IO.IaqOverRide) configured or the only 
configured sensor (via IO.SpaceCo2) has failed.
SrcIaqOvr
nvoIaqOvr
state
SW_OFF
SW_ON
SW_NUL
0
1
255
SW_NUL
M X
X
For IaqOvr.State, refer to IaqOvr.value.